3.  INTRINSIC SAFETY CERTIFICATION
3.1 ATEX certificate

The BA488CF has been issued with EC-Type
Examination Certificate by Notified Body  Intertek
Testing Services (ITS) confirming compliance with
the European ATEX Directive 94/9/EC for Group
II, Category 1, gas atmospheres, EEx ia IIC T4.
The instrument bears the Community Mark and,
subject to local codes of practice, may be installed
in any of the European Economic Area (EEA)
member countries.  ATEX certificates are also
acceptable for installations in Switzerland. This
manual describes installations which conform with
BS EN60079:Part14:1997 Electrical Installation in
Hazardous Areas.  When designing systems for
installation outside the UK, the local Code of
Practice should be consulted.

3.2  Zones, gas groups and T rating

The BA488CF has been issued with EC Type
Examination certificate ITS04ATEX22779
confirming that it complies with the requirements
for Group II Category 1 G EEx ia IIC T4 (Tamb –
40 to 60

o

C) specified in the ATEX Directive.

When connected to a suitable system the
BA488CF may be installed in:

Zone 0

explosive gas air mixture
continuously present.

Zone 1

explosive gas air mixture
likely to occur in normal
operation.

Zone 2

explosive gas air mixture not
likely to occur, and if it does
will only exist for a short time.

Be used with gases in groups:

Group   A    propane
Group   B    ethylene
Group   C    hydrogen

Having a temperature classification of:

T1

450oC

T2

300oC

T3

200oC

T4

135oC

At an ambient temperature between –40 and
+60

o

C.

Note

: the guaranteed operating temperature

range of the Fieldbus Display is –20 to +60

o

C

This allows the BA488CF to be installed in all
Zones and to be used with most common
industrial gases.

3.3   Fieldbus connection

The BA488CF Fieldbus Display is powered and
communicates via the fieldbus, which is

connected to terminals 1 and 2.  These terminals
comply with the Fieldbus Intrinsically Safe
Concept (FISCO) defined in IEC 60079 Part 27
which simplifies intrinsic safety system design.

The BA488CF may also be connected to non
FISCO compliant fieldbus segments by using the
entity concept to assess safety.

Terminals 1 and 2 of the BA488CF Fieldbus
Display are not polarised and have the following
safety parameters:

Ui

=

17.5V dc

Ii

=

380mA dc

Pi

=

5.32W

For non FISCO compliant segments, the safety
parameters of the power supply or isolator
powering the fieldbus segment must be equal to
or less than these figures.

The maximum equivalent capacitance and
inductance at terminals 1 & 2 of the BA488CF
Fieldbus Display are:

Ci

=        1nF

Li

=       8µH

To determine cable parameters for non FISCO
compliant segments, the sum of Ci and Li of all
the field devices should be subtracted from the
maximum cable parameters permitted by the
device powering the fieldbus segment.

3.4

  

External switches

For applications requiring operator inputs to be
made by large industrial push buttons, terminals
S1 to S7 facilitate external switches to be
connected to the Fieldbus Display.   When
external switches are connected, the BA488CF
may be configured so that the front panel push
buttons continue to function or are disabled.

Terminals S1 to S7 have the following combined
output safety parameters:

Uo

=

14.7V dc

Io

=

146.7mA dc

Po

=

0.58W

The switches and associated wiring connected to
the terminals must comply with the requirements
for 

simple apparatus

.  i.e. the switch must be

mechanically activated and  have IP20 protection,
and both the switch and the wiring must be
capable of withstanding a 500V rms insulation test
to earth for one minute.  Most industrial push
buttons and wiring satisfy these requirements.

The input safety parameters of terminals S1 to S7

Summary of Contents for BA484DF

Page 1: ...Issue 8 8th May 2006 BA488CF Intrinsically safe Panel mounting Fieldbus Display Issue 8...

Page 2: ...6 3 4 Units 6 3 5 Alarms 6 3 5 1 Alarm Summary 6 3 5 2 Alarm Activation 6 3 5 3 Alarm Output 6 3 6 Display 6 3 6 1 Settings 6 3 6 2 Quick Access 6 3 6 3 Access Code 6 3 7 Keys 6 3 8 Code 6 3 9 Unit In...

Page 3: ...88CF These switch inputs may also be used for returning the status of plant contacts The Fieldbus Display can be supplied with six optional alarm outputs that may be linked to any of the displayed fie...

Page 4: ...Profibus web sites or from the BEKA associates web site at www beka co uk Fig 1 Simplified block diagram of BA488CF 2 1 Controls The user can scroll through the display screens by operating the Up or...

Page 5: ...The BA488CF Fieldbus Display is powered and communicates via the fieldbus which is connected to terminals 1 and 2 These terminals comply with the Fieldbus Intrinsically Safe Concept FISCO defined in...

Page 6: ...m output is Ci 40nF Li 20 H To determine the maximum permissible cable parameters Ci and Li must be subtracted from the maximum cable capacitance and inductance specified by the system certificate of...

Page 7: ...ble of withstanding a 500V rms insulation test to earth for one minute Most industrial push buttons and wiring satisfy these requirements Although the allowable cable parameters are large it is recomm...

Page 8: ...he instrument secured with four panel mounting clips The BA488CF liquid crystal display has maximum contrast when viewed from directly ahead and slightly below the centre line of the instrument Fig 5...

Page 9: ...with the requirements of the European EMC Directive 89 336 EEC For specified immunity all wiring should be in screened twisted pairs To prevent circulating currents cable screens should only be earthe...

Page 10: ...sing the Up or Down button set the first digit of the code which will be flashing Pressing P will transfer control to the next digit which should be adjusted in the same way When all four digits have...

Page 11: ...Four variables vertical bargraphs 6 3 2 Input Settings Only included in Profibus PA and Fieldbus Foundation Revision 1 instruments Omitted from Fieldbus Foundation Revision 2 instruments because these...

Page 12: ...can contain up to sixteen alphanumeric characters This menu allows these tags to be entered After selecting the required variable the tag legend is entered character by character using the Up and Down...

Page 13: ...see 6 3 5 1 6 3 6 Display 6 3 6 1 Settings The backlight brilliance and display contrast are adjustable from this sub menu 6 3 6 2 Quick Access This sub menu enables the Quick Access Menu which is de...

Page 14: ...that the fieldbus function blocks selected are supported by the system host To change the BA488CF F revision highlight the required revision in the Restore Defaults menu and follow the screen prompts...

Page 15: ...15...

Page 16: ...ints Bargraph on standard display format is shown dotted Displayed fieldbus variable is outside bargraph limits or data is bad Bargraph limits see section 6 3 2 8 2 Fault finding after commissioning E...

Page 17: ...ult this guide if one of the nine standard display screens is being used The guide may be requested from the BEKA sales office or downloaded from the BEKA web site at www beka co uk 9 3 Fieldbus Inter...

Page 18: ...2 Fieldbus Connection 3 3 Foundation 1 2 Interface Guide 9 3 Revisions 1 2 6 3 10 3 FISCO 3 3 4 1 FM Approval Appendix 1 Gas groups 3 2 Appendix 1 2 Guarantee 8 5 IECEx Certification Appendix 2 Input...

Page 19: ...comply with the requirements for a FISCO Field Device specified in IEC60079 27 The intrinsically safe circuits shown in Figs 2 and 3 of this manual may therefore be used for installations in the USA...

Page 20: ...BA484DF and BA488CF Entity Parameters Terminals 1 2 Ui 17 5V Uo 0 Ii 380mA dc Io 0 Pi 5 32W Po 0 Ci 1nF Li 8 H These terminals comply with The Intrinsically Safe Concept FISCO defined by IEC 60079 27...

Page 21: ...galvanic Ccable Ci Lcable Li Ccable Ci Lcable Li Ccable Ci Lcable Li Intrinsically Safe Systems for Hazardous Classified Locations and the National Installation shall be in accordance with ANSI ISA RP...

Page 22: ...following table When installed in a hazardous classified location the BA484DF Fieldbus Display Any metallic or plastic cable gland or conduit hub that provides SSTG 1 STG 1 STAG 1 Permitted gland or...

Page 23: ...provide energy to the system except a leakage current of 50 A for each connected device Separately powered equipment needs galvanic isolation to ensure the intrinsically safety Fieldbus circuit remain...

Page 24: ...PTIONAL ALARM A8 A5 OPTIONAL ALARM A6 A3 OPTIONAL ALARM A4 A1 OPTIONAL ALARM A2 S6 S5 S4 S3 S2 S1 SEE NOTE 5 OPTIONAL EXTERNAL SWITCHES BA484DF and BA488CF Maximum input and output parameters Terminal...

Page 25: ...panel thickness should be 2mm 0 08inches Steel 3mm 0 12inches Aluminium Outside panel finish should be smooth free from particle inclusions runs or build up around cut out Panel cut out should be 66...

Page 26: ...II and III Class I Class Any metallic or plastic cable gland or conduit hub that provides the required environmental protection SSTG 1 STG 1 STAG 1 Crouse Hinds Myler hubs CMCXAA050 MCR050 MCX050 Per...

Page 27: ...allowed to provide energy to the system except a leakage current of 50 A for each connected device Separately powered equipment needs galvanic isolation to ensure the intrinsically safety Fieldbus ci...

Page 28: ...e following certification code and marking For gas Ex ia IIC T4 Ta 40o C to 60 o C The specified intrinsic safety parameters are identical to the ATEX parameters and confirm that terminals 1 2 comply...

Reviews: