BEKA BA484DF Manual Download Page 13

13

6.3.5.2  Alarm activation

Fieldbus variables that have not been validated
are displayed with dark characters on a light
background, and some screen formats also
contain a status indication.  This sub-menu allows
the alarm outputs to be conditioned so that they
only operate with validated fieldbus data, or to
operate irrespective of data validity.

6.3.5.3  Alarm output

There is a separate sub-menu for each of the six
alarm outputs; these link the alarm to one of the
displayed fieldbus variables and define the alarm
function and the setpoints.

To link the alarm to a displayed variable, position
the cursor over the ‘IN_n’ field, press 

P

 and using

the 

Up

 or 

Down

 button select the required input

source.  Enter the selection by pressing the 

E

button.

Each alarm output can be N/O or N/C in the non-
alarm condition.  To change the setting, position
the highlight over the ‘N/O’ or ‘N/C’ field, press 

P

and use the 

Up

 or 

Down

 button to toggle the

setting. Enter the selection by pressing the 

E

button.

Each alarm has three functions that can be
independently enabled to condition the output as
a low or high alarm, or as a combined low and
high alarm, either with or without hysteresis.

The required functions can be individually enabled
by positioning the highlight over the Enb/Dis
(Enabled/Disabled) column, pressing 

P

 and

toggling the function to the required state, then
entering the selection by pressing the 

E

 button.

Alarm setpoints are entered digit by digit.   Place
the highlight over the setpoint to be adjusted and
press 

P;

 the flashing digit to be adjusted may then

be selected by again pressing 

P

.  When all the

digits have been adjusted, operating the 

E

 button

enters the value and moves the menu up one
level.

The function of all alarms may be reviewed from
the alarm summary menu - see 6.3.5.1.

6.3.6  Display
6.3.6.1  Settings

The backlight brilliance and display contrast are
adjustable from this sub-menu.

6.3.6.2  Quick Access

This sub-menu enables the Quick Access Menu
which is described in sections 2.1 & 6.4   When
enabled, an operator can adjust the display
contrast and backlight brilliance without having
access to any other conditioning menus.

6.3.6.3  Access Code

Defines a four digit alphanumeric code that must
be entered to gain access to the Quick Access
Menu.   Alpha characters are case sensitive.
Default code 0000 allows direct access without a
code.

6.3.7  Keys

The function of the front panel push buttons may
be transferred to the six optional external push
buttons, with or without disabling the BA488CF
front panel push buttons.  The table below shows
the function of the BA488CF front panel and the
external push buttons for each of the four options
that may be selected in the Keys sub-menu.

* Apart from when ‘IPort’ is selected, the Key_Status
does not function when the instrument is in the configuration
menu.

The fourth option, ‘In Port’ allows the front
panel push buttons to be used for controlling the
BA488CF Fieldbus Display and the optional
external push buttons to independently enter
operator acknowledgements or controls.   This
option also allows the status of plant mechanical
switches to be returned to the host.

For applications where the instrument is only
displaying 1, 2, 3 or 4 variables on a single
screen, it is recommended that external buttons
are selected but not fitted.  This will disable the
instrument front panel buttons, but still provide
access to the configuration menu, which may be
protected by a security code.

6.3.8  Code

Defines the four digit alphanumeric code that must
be entered to gain access to the instrument
configuration menus. Alpha characters are case
sensitive. Default code 0000 allows direct access
without a code.

6.3.9  Unit Info

Displays the instrument model number and the
firmware version.

Summary of Contents for BA484DF

Page 1: ...Issue 8 8th May 2006 BA488CF Intrinsically safe Panel mounting Fieldbus Display Issue 8...

Page 2: ...6 3 4 Units 6 3 5 Alarms 6 3 5 1 Alarm Summary 6 3 5 2 Alarm Activation 6 3 5 3 Alarm Output 6 3 6 Display 6 3 6 1 Settings 6 3 6 2 Quick Access 6 3 6 3 Access Code 6 3 7 Keys 6 3 8 Code 6 3 9 Unit In...

Page 3: ...88CF These switch inputs may also be used for returning the status of plant contacts The Fieldbus Display can be supplied with six optional alarm outputs that may be linked to any of the displayed fie...

Page 4: ...Profibus web sites or from the BEKA associates web site at www beka co uk Fig 1 Simplified block diagram of BA488CF 2 1 Controls The user can scroll through the display screens by operating the Up or...

Page 5: ...The BA488CF Fieldbus Display is powered and communicates via the fieldbus which is connected to terminals 1 and 2 These terminals comply with the Fieldbus Intrinsically Safe Concept FISCO defined in...

Page 6: ...m output is Ci 40nF Li 20 H To determine the maximum permissible cable parameters Ci and Li must be subtracted from the maximum cable capacitance and inductance specified by the system certificate of...

Page 7: ...ble of withstanding a 500V rms insulation test to earth for one minute Most industrial push buttons and wiring satisfy these requirements Although the allowable cable parameters are large it is recomm...

Page 8: ...he instrument secured with four panel mounting clips The BA488CF liquid crystal display has maximum contrast when viewed from directly ahead and slightly below the centre line of the instrument Fig 5...

Page 9: ...with the requirements of the European EMC Directive 89 336 EEC For specified immunity all wiring should be in screened twisted pairs To prevent circulating currents cable screens should only be earthe...

Page 10: ...sing the Up or Down button set the first digit of the code which will be flashing Pressing P will transfer control to the next digit which should be adjusted in the same way When all four digits have...

Page 11: ...Four variables vertical bargraphs 6 3 2 Input Settings Only included in Profibus PA and Fieldbus Foundation Revision 1 instruments Omitted from Fieldbus Foundation Revision 2 instruments because these...

Page 12: ...can contain up to sixteen alphanumeric characters This menu allows these tags to be entered After selecting the required variable the tag legend is entered character by character using the Up and Down...

Page 13: ...see 6 3 5 1 6 3 6 Display 6 3 6 1 Settings The backlight brilliance and display contrast are adjustable from this sub menu 6 3 6 2 Quick Access This sub menu enables the Quick Access Menu which is de...

Page 14: ...that the fieldbus function blocks selected are supported by the system host To change the BA488CF F revision highlight the required revision in the Restore Defaults menu and follow the screen prompts...

Page 15: ...15...

Page 16: ...ints Bargraph on standard display format is shown dotted Displayed fieldbus variable is outside bargraph limits or data is bad Bargraph limits see section 6 3 2 8 2 Fault finding after commissioning E...

Page 17: ...ult this guide if one of the nine standard display screens is being used The guide may be requested from the BEKA sales office or downloaded from the BEKA web site at www beka co uk 9 3 Fieldbus Inter...

Page 18: ...2 Fieldbus Connection 3 3 Foundation 1 2 Interface Guide 9 3 Revisions 1 2 6 3 10 3 FISCO 3 3 4 1 FM Approval Appendix 1 Gas groups 3 2 Appendix 1 2 Guarantee 8 5 IECEx Certification Appendix 2 Input...

Page 19: ...comply with the requirements for a FISCO Field Device specified in IEC60079 27 The intrinsically safe circuits shown in Figs 2 and 3 of this manual may therefore be used for installations in the USA...

Page 20: ...BA484DF and BA488CF Entity Parameters Terminals 1 2 Ui 17 5V Uo 0 Ii 380mA dc Io 0 Pi 5 32W Po 0 Ci 1nF Li 8 H These terminals comply with The Intrinsically Safe Concept FISCO defined by IEC 60079 27...

Page 21: ...galvanic Ccable Ci Lcable Li Ccable Ci Lcable Li Ccable Ci Lcable Li Intrinsically Safe Systems for Hazardous Classified Locations and the National Installation shall be in accordance with ANSI ISA RP...

Page 22: ...following table When installed in a hazardous classified location the BA484DF Fieldbus Display Any metallic or plastic cable gland or conduit hub that provides SSTG 1 STG 1 STAG 1 Permitted gland or...

Page 23: ...provide energy to the system except a leakage current of 50 A for each connected device Separately powered equipment needs galvanic isolation to ensure the intrinsically safety Fieldbus circuit remain...

Page 24: ...PTIONAL ALARM A8 A5 OPTIONAL ALARM A6 A3 OPTIONAL ALARM A4 A1 OPTIONAL ALARM A2 S6 S5 S4 S3 S2 S1 SEE NOTE 5 OPTIONAL EXTERNAL SWITCHES BA484DF and BA488CF Maximum input and output parameters Terminal...

Page 25: ...panel thickness should be 2mm 0 08inches Steel 3mm 0 12inches Aluminium Outside panel finish should be smooth free from particle inclusions runs or build up around cut out Panel cut out should be 66...

Page 26: ...II and III Class I Class Any metallic or plastic cable gland or conduit hub that provides the required environmental protection SSTG 1 STG 1 STAG 1 Crouse Hinds Myler hubs CMCXAA050 MCR050 MCX050 Per...

Page 27: ...allowed to provide energy to the system except a leakage current of 50 A for each connected device Separately powered equipment needs galvanic isolation to ensure the intrinsically safety Fieldbus ci...

Page 28: ...e following certification code and marking For gas Ex ia IIC T4 Ta 40o C to 60 o C The specified intrinsic safety parameters are identical to the ATEX parameters and confirm that terminals 1 2 comply...

Reviews: