7. LINEARISER
The BA337E-SS Rate Totaliser includes a sixteen
segment straight-line lineariser which can compensate
for non-linearity resulting from a flowmeter having a
K-factor that varies with the flow rate, such as a
turbine meter used over a wide range of flows.
The lineariser is enabled by selecting
Lin
in the
FunCtion
section of the configuration menu. The
configuration menu shown in Fig 13 remains basically
unchanged, except that up to 16 values of the
flowmeter K-factor can be entered as
l-factor
,
together with
pul5e fr
the corresponding input
frequency at which each starts.
Fig 15 shows how the Rate Totaliser configuration
function
FACtor
is extended when the lineariser is
activated by selecting
Lin
in the
FunCtion
menu.
Fig 14 shows a typical linearising characteristic
The lineariser configuration is retained irrespective of
how
FunCtion
in the Rate Totaliser configuration
menu is subsequently changed. It is therefore
possible to select and deselect the lineariser without
having to reconfigure it.
7.1 Flowmeter specification
Flowmeters are usually supplied with a calibration
certificate specifying the average K-factor and the
flow range over which it applies. For use over
extended flow ranges and for non-linear devices,
multiple K-factors will be specified, often in a table
similar to the one shown below.
Flow Rate
Litres/min
K-factor
Pulses/litre
5
200
10
230
15
239
20
242
From this calibration certificate information the
output frequency of the flowmeter, which is required
for conditioning the Rate Totaliser lineariser, can be
calculated.
Output frequency Hz = (Flow rate per min) x (K-factor)
60
Flow Rate
Litres/min
K-factor
Pulses/litre
Output
frequency
Hz
0
0
0
5
200
16.666
10
230
38.333
15
239
59.750
20
242
80.666
7.2 Summary of lineariser configuration
Functions.
This section summarises the lineariser configuration
functions. When read in conjunction with Fig 15 it
provides a quick aid for configuring the lineariser. If
more detail is required, each section contains a
reference to a full description of the function.
The number of straight-line lineariser segments
required should first be entered using the
Add
and
del
functions. In both of these sub-functions the
Rate Totaliser displays the current segment and the
total number of segments being used as shown
below.
Increasing the number of segments will provide a
more accurate approximation of the flowmeter
characteristic and increase totalisation accuracy.
31
Summary of Contents for BA337E-SS
Page 4: ...4...
Page 24: ...24...
Page 25: ...25...
Page 32: ...32...
Page 42: ...42...
Page 54: ...54...
Page 55: ...55...
Page 56: ...56...
Page 57: ...57...
Page 58: ...58...
Page 59: ...59...
Page 60: ...60...
Page 61: ...61...
Page 62: ...62...
Page 63: ...63...
Page 64: ...64...
Page 65: ...65...