8
b. The flowmeter and associated wiring can
withstand a 500V rms insulation test to earth.
c. The flowmeter is located in the same
hazardous area as the BA334G. The BA334G
EU-Type Examination Certificate specifies that
the equivalent capacitance and inductance of
pulse input is:
Ci
=
2nF
Li
=
4µH
To determine the maximum permissible cable
parameters these figures should be subtracted from
the maximum permitted output parameters Lo and
Co specified by the certificate for the flowmeter
connected to the totaliser's pulse input terminals.
The totalisers pulse input equivalent capacitance
and inductance are small and unlikely to make a
significant difference to the allowable cable
parameters.
3.4.2 Flowmeter sensors requiring energising
Flowmeters with switch contacts, proximity detector
or open collector outputs require energising which is
achieved by linking Rate Totaliser terminals 3 and 4
together as described in section 3.4. When
energised, the output parameters of the pulse input
terminals 5 and 6 are:
Uo
=
10.5V dc
Io
=
9.2mA dc
Po
=
24mW
These output parameters do not comply with the
requirements for
simple apparatus
and should be
considered when assessing the safety of the
flowmeter connected to the totaliser pulse input.
Any certified intrinsically safe flowmeter may be
connected to a BA334G energised input providing
that:
a. The flowmeter is a certified intrinsically safe
device having input parameters equal to or
greater than:
Uo
≥
10.5V dc
Io
≥
9.2mA dc
Po
≥
24mW
or
complies with the requirements for
simple apparatus.
b. The flowmeter and associated wiring can
withstand a 500V rms insulation test to earth.
c. The flowmeter is located in the same
hazardous area as the BA334G.
d. Minimum operating voltage of a flowmeter
incorporating a proximity detector is less than
7.5V.
e. The maximum capacitance and inductance
that may be safely connected to the
energised pulse input terminals 5 & 6
(terminals 3 & 4 linked) is:
Co
=
2.4µF
Lo
=
200mH
This is not restrictive as the combined capacitance
and inductance of most sensors and the
connecting cable will be less than this.
3.5
Remote reset terminals
The BA334G total display may be reset to zero by
connecting the external reset terminals RS1 and
RS2 together for more than one second. The two
reset terminals have the following input and output
safety parameters:
Uo
=
3.8V dc
Io
=
1mA
Po
=
1mW
Ui
=
28V dc
Ii
=
200mA dc
Pi
=
0.84W
The equivalent capacitance and inductance
between them is:
Ci
=
0
Li
=
0
The maximum cable capacitance and inductance
that may be safely connected between the reset
terminals RS1 and RS2 is:
Co
=
40µF
Lo
=
1H
The reset terminals may be directly connected to
any mechanically operated switch located within
the same hazardous area as the BA334G Rate
Totaliser. The switch and associated wiring should
be able to withstand a 500V rms insulation test to
earth.
Summary of Contents for BA334E
Page 22: ...22 ...
Page 23: ...23 ...
Page 32: ...32 ...
Page 43: ...43 ...
Page 51: ...51 ...
Page 52: ...52 ...
Page 53: ...53 ...
Page 54: ...54 ...
Page 55: ...55 ...
Page 56: ...56 ...
Page 57: ...57 ...
Page 58: ...58 ...
Page 59: ...59 ...
Page 60: ...60 ...
Page 61: ...61 ...
Page 62: ...62 ...