background image

23

9.3.10  Alarm silence time:   SiL

This function is primarily intended for use in small
installations  where  the  alarm  output  directly
operates an alarm annunciator such as a sounder
or beacon.  When the alarm silence time, which is
adjustable  between  0  and  3600  seconds  in  1
second increments, is set to any figure other than
zero, the 

P

 push-button becomes an alarm accept

button.   After an alarm has occurred, operating the

P

 button will cause the alarm output to revert to the

non-alarm  condition  for  the  programmed  alarm
silence time.  If the alarm condition still exists at
the end of the silence time, the alarm output will be
reactivated.  During the silence time the indicator
alarm annunciator will flash until the silence time
expires or the alarm is cleared. 

If the ‘FLSH’ function, which flashes the indicator
display when an alarm occurs has been enabled,
it  will  only  function  when  the  alarm  output  is
activated, not during the silence time.  See section
9.3.11

To adjust the alarm silence time select 'SiL' from
the alarm configuration menu and press  

P

 which

will reveal the existing silence time.  The flashing
digit of the silence time can be adjusted using the

 and 

 push-buttons, and the 

P

 button to move

control  to  the  other  digits.    When  the  required
silence time has been entered press 

E

 

to return to

the alarm menu.

9.3.11 Flash display when alarm occurs

 

‘FLSH’

In addition to the two alarm annunciators on the
top left hand corner of the indicator display which
show  the  status  of  both  alarms,  this  function
provides an even more conspicuous indication that
an alarm condition has occurred.    

When enabled, the function alternates the indicator
display between the numerical value and the alarm
reference, ‘ALr1’ or ‘ALr2’, when the alarm output
is activated.  If both alarm outputs are activated,
the alarm references are displayed in sequence.

To  enable  or  disable  the  function  select  'FLSH'
from the alarm menu and press 

P

 which will reveal

the current setting ‘on’ or ‘oFF’.  The function can
changed by pressing the 

 or 

 button followed

by the 

E

 button to return to the alarm menu.

9.3.12 Access setpoint in display mode:  ACSP

This function enables a separate menu providing
access  to  the  alarm  setpoints  from  the  display
mode  by  simultaneously  operating  the  

P

 and  

push-buttons.  An operator can therefore adjust the
alarm  setpoints  without  having  access  to  the
indicator  configuration  menu.    Protection  against
accidental  adjustment  of  the  setpoints  when  the

indicator is in the display mode is provided by a
separate security code.

This direct setpoint access menu is enabled and
the  separate  security  code  entered  from  the
'ACSP' function in the alarm configuration menu as
shown in Fig 12.  To change the menu parameters
select  'ACSP'  from  the  configuration  menu  and
press  

P

 

which   will   display   the   enable   prompt

'EnbL'.  Press 

P

 again to reveal if the direct access

menu  is  'on'  or  'oFF'.    The  

 or  

 button  will

toggle the display between the two conditions.  

If  'oFF'  is  selected,  the  operator  will  not  have
access  to  the  setpoints  from  the  display  mode.
Return to the 'ACSP' prompt in the main menu by
pressing

 

E

 twice.  

If  'on'  is  selected,  the  operator  will  have  direct
access  to  the  alarm  setpoints  from  the  display
mode via a separate optional security code.   To
define this four digit security code press 

P

 to return

to the 'Enbl' prompt followed by the 

 or 

 button

to  select  the  access  code  prompt  'ACCd'.
Pressing  

P

 

will  reveal  the  current  security  code.

Each  digit  of  the  code  may  be  changed  by
operating the 

 and 

 push-buttons, and the  

P

button to move control to the next digit.  When the
required code has been entered, press 

E

 twice to

return  to  the  'ACSP'  prompt  in  the  configuration
menu.

Default  code  0000  will  disable  the  security  code
allowing  direct  access  to  the  setpoints  in  the
display  mode  by  pressing  the

 

P

 

and  

 buttons

simultaneously.  Unless otherwise requested new
instruments  with  alarms  are  supplied  with  this
function  disabled  and  the  security  code  set  to
0000.

9.3.13  Adjusting alarm setpoints from the
            display mode

Access  to  the  alarm  setpoints from  the  indicator
display mode is obtained by operating the 

P

 and 

push-buttons simultaneously as shown in Fig 13.  If
the setpoints are not protected by a security code
the alarm setpoint prompt 'SP1' will be displayed.
If the setpoints are protected by a security code,
'Code' will be displayed first.  Pressing 

P

 again will

enable the alarm security code to be entered digit
by digit using the 

 and 

 buttons to change the

flashing  digit,  and  the  

P

 push-button  to  move

control  to  the  next  digit.    If  the  correct  code  is
entered  pressing  

E

 

will  cause  alarm  setpoint

prompt 'SP1' to be displayed.  Pressing the 

 or

 button will toggle the display between the two

alarm setpoint prompts 'SP1' and 'SP2'.

If an incorrect security code is entered, or a button
is not pressed within twenty seconds, the indicator
will automatically return to the display mode.

Summary of Contents for BA304E

Page 1: ...Issue 8 5th May 2016 BA304E BA324E intrinsically safe loop powered field mounting indicators Issue 8 ...

Page 2: ...eariser error message 7 4 Lineariser default configuration 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine maintenance 8 5 Guarantee 8 6 Customer comments 9 Accessories 9 1 External keypad 9 2 Units of measurement and instrument identification 9 3 Alarms 9 3 1 Solid state output 9 3 2 Intrinsic safety 9 3 3 Configuration and adju...

Page 3: ...Type Examination certificate specifies that under fault conditions the output voltage current and power at the 4 20mA input terminals will not exceed those specified for simple apparatus in Clause 5 7 of EN 60079 11 which simplifies installation and documentation For international applications both models have IECEx certification which is described in Appendix 2 For installations in the USA and Ca...

Page 4: ...ation ATEX dust and IECEx approvals are described in Appendixes 1and 2 3 1 ATEX gas certification Notified Body Intertek Testing and Certification Ltd have issued both models with a common EC Type Examination Certificate number ITS11ATEX27253X This confirms compliance with harmonised European standards and it has been used to confirm compliance with the European ATEX Directive for Group II Categor...

Page 5: ... ATEX certification information and BEKA associates name and location Non European certification information may also be shown The instrument serial number and date of manufacturer are recorded on a separate label inside the terminal compartment BA304E certification label BA324E certification label 4 SYSTEM DESIGN FOR GAS HAZARDOUS AREAS 4 1 Transmitter loops Both models may be connected in series...

Page 6: ...he indicator plus the interface When a high integrity earth connection is already available a Zener barrier is usually the least expensive option If an earth connection is not available or isolation is required a galvanic isolator is the correct choice If one side of the 4 20mA current loop may be earthed a single channel Zener barrier provides the lowest cost protection If the 4 20mA signal is no...

Page 7: ...thed post or structure the earth terminal should be connected to the plant potential equalising conductor The enclosures are fitted with a bonding plate to ensure electrical continuity between the three conduit cable entries 5 2 Installation Procedure Fig 4 illustrates the instrument installation procedure a Remove the instrument terminal cover by unscrewing the two captive A screws b Mount the in...

Page 8: ...ation Default Configuration BA304E BA324E Access code CodE 0000 0000 Function FunC Linear Linear Display at 4mA Zero 0 0 0 00 Display at 20mA SPAn 100 0 100 00 Resolution rESn 1 digit 1 digit Bargraph start BarLo 0 00 Bargraph finish BarHi 100 00 P button in display mode C P Tare tArE Off Off 6 1 Summary of configuration functions This section summarises each of the main configuration functions an...

Page 9: ...9 ...

Page 10: ...Lin 16 segment adjustable lineariser To reveal the existing indicator function select FunC from the configuration menu and press P If the function is set as required press E to return to the menu or press the or button to change the setting followed by the E button to return to the configuration menu Std Linear Provides a linear relationship between the 4 20mA indicator input current and the indic...

Page 11: ...between the two currents is greater than 4mA If these conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the instrument will be reverse acting i e an increasing input current will cause the display to decrease 6 6 Calibration using internal reference SEt Using the SEt function the indicator can be calibrate...

Page 12: ...setting between on and oFF When set as required press E to return to the tARE prompt in the configuration menu 6 10 Security code CodE Access to the instrument configuration menu may be protected by a four digit security code which must be entered to gain access New instruments are configured with the default security code 0000 which allows unrestricted access to all configuration functions To ent...

Page 13: ...direct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this method also allows direct calibration from the variable to be displayed e g the output from a level sensor in an irregular tank may be displayed in linear volumetric units by filling the tank with known incremental volumes ...

Page 14: ...14 ...

Page 15: ...ollowing break point 7 1 1 Example Adding break points to a new indicator When adding break points to a new indicator or to a lineariser following resetting to the factory defaults using the LtAb function described in section 6 11 each additional break point should be added before the highest existing breakpoint The first additional break point should be added before the default break point 1 1 wh...

Page 16: ...nction by pressing the E button The corresponding indicator display at each of the break points can now be defined using the diSP sub function Using the and buttons select the diSP sub function and press P which will reveal the starting point for the first break point 0 n where n is the total number of break points entered Press P and use the and buttons and the P button to move between digits to ...

Page 17: ... indicator fails after it has been functioning correctly follow the procedure shown in section 8 1 If this does not reveal the cause of the fault it is recommended that the instrument is replaced This can be done without disconnecting power but while the indicator is disconnected the 4 20mA loop will be open circuit 8 3 Servicing All BA304E and BA324E loop powered indicators are interchangeable if...

Page 18: ...on Both indicators can also be supplied with a blank or custom laser engraved stainless steel plate secured by two screws to the front of the instrument enclosure This plate can accommodate 1 row of 9 alphanumeric characters 10mm high or 1 row of 11 alphanumeric characters 7mm high or 2 rows of 18 alphanumeric characters 5mm high 9 3 Alarms CAUTION These alarms outputs should not be used for criti...

Page 19: ...ied by clause 5 7 of EN 60079 11 for simple apparatus This simplifies system documentation and allows the alarm output terminals 8 9 and 10 11 to be connected to almost any intrinsically safe circuit protected by a Zener barrier or galvanic isolator providing the output parameters of the circuit do not exceed Uo 30V dc Io 200mA Po 0 84W The maximum equivalent capacitance and inductance between eac...

Page 20: ...20 ...

Page 21: ...setpoint The alarm is activated when the indicator display equals the setpoint See section 9 3 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 3 6 no nC Normally open or normally closed output Sets the alarm output open or closed in the non alarm condition See section 9 3 7 HStr Hysteresis Adjusts the alarm hysteresis See section 9 3 8 dELA Alarm delay time Introduce...

Page 22: ...or fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and press P to reveal the setting The function may be changed by pressing the or button followed by the E button to return to the alarm configuration menu 9 3 8 Hysteresis HStr Hysteresis is shown in the units...

Page 23: ...aving access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This direct setpoint access menu is enabled and the separate security code entered from the ACSP function in the alarm configuration menu as shown in Fig 12 To change the menu parameters select ACSP from the con...

Page 24: ...oint plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 14 Fig 14 Displayed value and setpoints on bargraph The bargraph area below the low alarm setpoint and the area above the high alarm setpoint are activated The displayed variable is represented by an activated bar which moves between these low and ...

Page 25: ...those specified by clause 5 7 of EN 60079 11 for simple apparatus which simplifies system design and documentation Providing the increased voltage drop can be tolerated the intrinsic safety and system design described in sections 3 and 4 of this manual remain valid with the backlight loop powered 9 4 2 Separately powering the backlight The optional backlight may also be powered from a separate saf...

Page 26: ...al pipe BA392D Stainless steel bracket secured by two worm drive hose clips Will clamp to any vertical or horizontal pipe with an outside diameter between 60 and 80mm BA393 Heavy duty stainless steel bracket secured by a single V bolt Will clamp to any vertical or horizontal pipe with an outside diameter between 40 and 80mm ...

Page 27: ... in normal operation but if it does occur will only persist for a short period Be used with dust in subdivisions IIIA combustible flyings IIIB non conductive dust IIIC conductive dust Having a Minimum Ignition Temperature of Dust cloud 120 C Dust layer on indicator 155 C up to 5mm thick Dust layer on indicator Refer to over 5mm thick EN 61241 14 At an ambient temperature between 40 and 70 C A1 2 C...

Page 28: ... apply when the indicator is installed in Zone 1 or in Zone 2 The specified IECEx gas and dust intrinsic safety parameters are identical to the ATEX safety parameters described in the main section and Appendix 1 of this manual The IECEx certificate may be downloaded from www beka co uk www iecex com or requested from the BEKA sales office A2 2 Installation The IECEx and ATEX certificates specify i...

Page 29: ...rinsically Safe Systems for Hazardous Classified Locations and with the National Electrical Code ANSI NFPA70 Installations in Canada must comply with the Canadian Electrical Code C22 2 The BA304E and BA324E have T5 rating at ambient temperatures up to 70ºC and may be used with the following gases and dusts Intrinsic Safety Division 1 or 2 Class I Group A B Group C Group D Class II Group E F G Clas...

Page 30: ...30 ...

Page 31: ...31 ...

Page 32: ...32 ...

Page 33: ...33 ...

Page 34: ...34 ...

Page 35: ...35 ...

Page 36: ...36 ...

Page 37: ...37 ...

Page 38: ...38 ...

Page 39: ...39 ...

Page 40: ...40 ...

Reviews: