background image

15

The delete break-point sub-function 'dEL' operates
in exactly the same way as the 'Add' sub-function
described  above.      Once  within  the  ‘dEL’  sub-
function each time the 

P

 button is pressed a break-

point  is  removed.    When  deleting  a  break-point
from a calibrated indicator, the break-point to be
deleted can be selected using the 

 and 

 push

buttons.  The minimum number of break-point is 2,
break-points '0

:

1' and '1

:

1'.  

When  the  required  number  of  linearising  break-
points has been entered, return to the linearisation
sub-menu by pressing 

E

.  

The indicator will display

the 'Add' or 'dEL' prompt depending upon the last
function used.    Using the 'Pts' sub-function the
input current at which each break-point occurs and
the  corresponding  indicator  display  may  now  be
defined.

Using the 

 or 

 button select the  'PtS' function

in the sub-menu and press 

P

  to enter the function

which will display the first break-point '0

:

n', where n

is  the  total  number  of  linearising  break-points
entered   –   see   Fig   7.     The   selected   linearising
break-point can be changed using the 

 and 

buttons.  When the required linearising break-point
has been selected set the indicator input current to
the exact value at which the break-point is required
and press  

P

*

.   Using the 

 and 

 buttons and

the  

P

  button  to  move  between  digits,  enter  the

required  indicator  display  at  this  break-point.
When set as required, press the 

E

 

push button

 

to

enter the required indicator display and return to
the sub-menu from which the next beak-point can
be selected.   

When  all  the  break-points  have  been  calibrated
pressing  

E

 

twice  will  return  the  indicator  to  the

‘CAL’ function in the configuration menu.

Note:

   * 

The   indicator   input   current   must   be

  adjusted to the required value before the 

P

button  is  operated to  enter the required  
indicator display.

Error message

If during calibration  the indicator displays a
'FAiL' error message the current at which the
selected break-point is being set is not above
the proceeding break-point or is not below the
following break-point.

7.1.1  Example 
          Adding break-points to a new indicator

When adding break-points to a new indicator, or to
a  lineariser  following  resetting  to  the  factory
defaults  using  the  'LtAb'  function  described  in
section 6.11, each additional break-point should be
added  before  the  highest  existing  breakpoint.
The  first  additional  break-point  should  be  added
before the default break-point '1

:

1' which will result

in a display of '1

:

2'.   If more new break-points are

required,  using  the  

 button  select  the  new

highest  break-point  '2

:

2'  and  add  the  second

additional  break-point  by  operating  the  

P

 push

button which will result in a display of '2

:

3'.  Repeat

the sequence until the required number of break-
points has been entered.   

The input current and at which each break-point
occurs  and  the  corresponding  indicator  display
may now be entered as described above. 

7.2  Lineariser calibration using the internal 
       reference.

The  ‘SEt’  function  enables  the  lineariser  to  be
calibrated  without  the  need  for  an  accurate
external current source.  Throughout the calibration
the  indicator  input  current  may  be  any  value
between 4 and 20mA.    

The ‘SEt’ functions contains four sub-functions. 

Display

      Description of function

'Add'

Add a break-point

Adds  a  new  break-point  before  the
displayed break-point.  The calibration
of existing break-points is not changed,
but  the  identification  number  of  all
subsequent break-point is increased by
one.

'dEL'

Remove a break-point

Removes  the  displayed  break-point
and joins the preceding segment to the
following  segment  with  a straight  line.
The  identification  number  of  all
subsequent  break-points  is  decreased
by one.

'in' 

Defines the current at which break-
point occurs.

Enables  the  required  current  at  each
break-point  to  be  defined  without
having  to  input  an  accurate  input
current to the indicator.

'diSP'

Defines  indicator  display  at  break-
point.

Enables  the  indicator  display  at  each
break-point to be defined.

The number of break-point required should first be
entered using the 'Add' and 'dEL'  sub-functions.
In  both  these  sub-functions  the  indicator  initially
displays  the  current  break-point  and  the  total
number of break-point being used as shown below.

Summary of Contents for BA304E

Page 1: ...Issue 8 5th May 2016 BA304E BA324E intrinsically safe loop powered field mounting indicators Issue 8 ...

Page 2: ...eariser error message 7 4 Lineariser default configuration 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine maintenance 8 5 Guarantee 8 6 Customer comments 9 Accessories 9 1 External keypad 9 2 Units of measurement and instrument identification 9 3 Alarms 9 3 1 Solid state output 9 3 2 Intrinsic safety 9 3 3 Configuration and adju...

Page 3: ...Type Examination certificate specifies that under fault conditions the output voltage current and power at the 4 20mA input terminals will not exceed those specified for simple apparatus in Clause 5 7 of EN 60079 11 which simplifies installation and documentation For international applications both models have IECEx certification which is described in Appendix 2 For installations in the USA and Ca...

Page 4: ...ation ATEX dust and IECEx approvals are described in Appendixes 1and 2 3 1 ATEX gas certification Notified Body Intertek Testing and Certification Ltd have issued both models with a common EC Type Examination Certificate number ITS11ATEX27253X This confirms compliance with harmonised European standards and it has been used to confirm compliance with the European ATEX Directive for Group II Categor...

Page 5: ... ATEX certification information and BEKA associates name and location Non European certification information may also be shown The instrument serial number and date of manufacturer are recorded on a separate label inside the terminal compartment BA304E certification label BA324E certification label 4 SYSTEM DESIGN FOR GAS HAZARDOUS AREAS 4 1 Transmitter loops Both models may be connected in series...

Page 6: ...he indicator plus the interface When a high integrity earth connection is already available a Zener barrier is usually the least expensive option If an earth connection is not available or isolation is required a galvanic isolator is the correct choice If one side of the 4 20mA current loop may be earthed a single channel Zener barrier provides the lowest cost protection If the 4 20mA signal is no...

Page 7: ...thed post or structure the earth terminal should be connected to the plant potential equalising conductor The enclosures are fitted with a bonding plate to ensure electrical continuity between the three conduit cable entries 5 2 Installation Procedure Fig 4 illustrates the instrument installation procedure a Remove the instrument terminal cover by unscrewing the two captive A screws b Mount the in...

Page 8: ...ation Default Configuration BA304E BA324E Access code CodE 0000 0000 Function FunC Linear Linear Display at 4mA Zero 0 0 0 00 Display at 20mA SPAn 100 0 100 00 Resolution rESn 1 digit 1 digit Bargraph start BarLo 0 00 Bargraph finish BarHi 100 00 P button in display mode C P Tare tArE Off Off 6 1 Summary of configuration functions This section summarises each of the main configuration functions an...

Page 9: ...9 ...

Page 10: ...Lin 16 segment adjustable lineariser To reveal the existing indicator function select FunC from the configuration menu and press P If the function is set as required press E to return to the menu or press the or button to change the setting followed by the E button to return to the configuration menu Std Linear Provides a linear relationship between the 4 20mA indicator input current and the indic...

Page 11: ...between the two currents is greater than 4mA If these conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the instrument will be reverse acting i e an increasing input current will cause the display to decrease 6 6 Calibration using internal reference SEt Using the SEt function the indicator can be calibrate...

Page 12: ...setting between on and oFF When set as required press E to return to the tARE prompt in the configuration menu 6 10 Security code CodE Access to the instrument configuration menu may be protected by a four digit security code which must be entered to gain access New instruments are configured with the default security code 0000 which allows unrestricted access to all configuration functions To ent...

Page 13: ...direct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this method also allows direct calibration from the variable to be displayed e g the output from a level sensor in an irregular tank may be displayed in linear volumetric units by filling the tank with known incremental volumes ...

Page 14: ...14 ...

Page 15: ...ollowing break point 7 1 1 Example Adding break points to a new indicator When adding break points to a new indicator or to a lineariser following resetting to the factory defaults using the LtAb function described in section 6 11 each additional break point should be added before the highest existing breakpoint The first additional break point should be added before the default break point 1 1 wh...

Page 16: ...nction by pressing the E button The corresponding indicator display at each of the break points can now be defined using the diSP sub function Using the and buttons select the diSP sub function and press P which will reveal the starting point for the first break point 0 n where n is the total number of break points entered Press P and use the and buttons and the P button to move between digits to ...

Page 17: ... indicator fails after it has been functioning correctly follow the procedure shown in section 8 1 If this does not reveal the cause of the fault it is recommended that the instrument is replaced This can be done without disconnecting power but while the indicator is disconnected the 4 20mA loop will be open circuit 8 3 Servicing All BA304E and BA324E loop powered indicators are interchangeable if...

Page 18: ...on Both indicators can also be supplied with a blank or custom laser engraved stainless steel plate secured by two screws to the front of the instrument enclosure This plate can accommodate 1 row of 9 alphanumeric characters 10mm high or 1 row of 11 alphanumeric characters 7mm high or 2 rows of 18 alphanumeric characters 5mm high 9 3 Alarms CAUTION These alarms outputs should not be used for criti...

Page 19: ...ied by clause 5 7 of EN 60079 11 for simple apparatus This simplifies system documentation and allows the alarm output terminals 8 9 and 10 11 to be connected to almost any intrinsically safe circuit protected by a Zener barrier or galvanic isolator providing the output parameters of the circuit do not exceed Uo 30V dc Io 200mA Po 0 84W The maximum equivalent capacitance and inductance between eac...

Page 20: ...20 ...

Page 21: ...setpoint The alarm is activated when the indicator display equals the setpoint See section 9 3 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 3 6 no nC Normally open or normally closed output Sets the alarm output open or closed in the non alarm condition See section 9 3 7 HStr Hysteresis Adjusts the alarm hysteresis See section 9 3 8 dELA Alarm delay time Introduce...

Page 22: ...or fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and press P to reveal the setting The function may be changed by pressing the or button followed by the E button to return to the alarm configuration menu 9 3 8 Hysteresis HStr Hysteresis is shown in the units...

Page 23: ...aving access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This direct setpoint access menu is enabled and the separate security code entered from the ACSP function in the alarm configuration menu as shown in Fig 12 To change the menu parameters select ACSP from the con...

Page 24: ...oint plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 14 Fig 14 Displayed value and setpoints on bargraph The bargraph area below the low alarm setpoint and the area above the high alarm setpoint are activated The displayed variable is represented by an activated bar which moves between these low and ...

Page 25: ...those specified by clause 5 7 of EN 60079 11 for simple apparatus which simplifies system design and documentation Providing the increased voltage drop can be tolerated the intrinsic safety and system design described in sections 3 and 4 of this manual remain valid with the backlight loop powered 9 4 2 Separately powering the backlight The optional backlight may also be powered from a separate saf...

Page 26: ...al pipe BA392D Stainless steel bracket secured by two worm drive hose clips Will clamp to any vertical or horizontal pipe with an outside diameter between 60 and 80mm BA393 Heavy duty stainless steel bracket secured by a single V bolt Will clamp to any vertical or horizontal pipe with an outside diameter between 40 and 80mm ...

Page 27: ... in normal operation but if it does occur will only persist for a short period Be used with dust in subdivisions IIIA combustible flyings IIIB non conductive dust IIIC conductive dust Having a Minimum Ignition Temperature of Dust cloud 120 C Dust layer on indicator 155 C up to 5mm thick Dust layer on indicator Refer to over 5mm thick EN 61241 14 At an ambient temperature between 40 and 70 C A1 2 C...

Page 28: ... apply when the indicator is installed in Zone 1 or in Zone 2 The specified IECEx gas and dust intrinsic safety parameters are identical to the ATEX safety parameters described in the main section and Appendix 1 of this manual The IECEx certificate may be downloaded from www beka co uk www iecex com or requested from the BEKA sales office A2 2 Installation The IECEx and ATEX certificates specify i...

Page 29: ...rinsically Safe Systems for Hazardous Classified Locations and with the National Electrical Code ANSI NFPA70 Installations in Canada must comply with the Canadian Electrical Code C22 2 The BA304E and BA324E have T5 rating at ambient temperatures up to 70ºC and may be used with the following gases and dusts Intrinsic Safety Division 1 or 2 Class I Group A B Group C Group D Class II Group E F G Clas...

Page 30: ...30 ...

Page 31: ...31 ...

Page 32: ...32 ...

Page 33: ...33 ...

Page 34: ...34 ...

Page 35: ...35 ...

Page 36: ...36 ...

Page 37: ...37 ...

Page 38: ...38 ...

Page 39: ...39 ...

Page 40: ...40 ...

Reviews: