Fig 12 Typical alarm application
(Shown without recommended screen cables)
7.3.2 Configuration and adjustment
When optional alarms are fitted the A90-SS panel
meter configuration menu is extended as shown in
Fig 11. For simplicity Fig 11 only shows the
additional functions for alarm 1, but alarm 2 has
identical functions.
The following table summarises each of the alarm
configuration functions and includes a cross
reference to more detailed information. Again only
the functions on alarm 1 are listed, but alarm 2 has
identical facilities.
Display
Summary of function
EnbL
Alarm enable
Enables or disables the alarm without
changing the alarm parameters.
See section 7.3.3
5P1
Setpoint adjustment
Adjusts the alarm setpoint. The alarm
is activated when the meter display
equals the setpoint.
See section 7.3.4
Display
Summary of function
Hi.
Lo
Alarm function
Defines the alarm function as High or
Low.
See section 7.3.5
nd
.
nE
Alarm relay energised or
de-energised in non alarm condition.
Determines whether the alarm relay is
energised or de-energised in the
non alarm condition.
See section 7.3.6
H5tr
Hysteresis
Adjusts the alarm hysteresis.
See section 7.3.7
dELA
Alarm delay
Introduces adjustable delay between
the display equalling the setpoint and
the alarm being activated.
See section 7.3.8
5iL
Alarm silence time
Defines the time that the alarm output
remains in the non-alarm condition
following acceptance of an alarm.
See section 7.3.9
FLA5H
Flash display when alarm occurs
When enabled, alternates the A90-SS
meter display between the process
value and the alarm reference,
ALr1
or
ALr2
, when an alarm output is
activated.
See section 7.3.10
latch
Latch alarm output
When enabled, maintains alarm output
until the alarm is manually cleared by
operating the
(
button.
See section 7.3.11
Color
Display colour in Alarm condition
Defines the colour of the A90-SS panel
meter display when an alarm occurs.
See section 7.3.12
AC5P
Access to setpoint in display mode
Sub-menu which enables direct access
to the alarm setpoints from the A90-SS
meter display mode, and defines a
separate security code.
See section 7.3.13