BEINAT SGM600 Manual Download Page 6

Page  6

Test  after  replacing  the  sensor.

Reconnect  the  power,  the  probe  starts  blinking  to  the  waiting  time  (Warm-up).
After  waiting  you  can  proceed  to  test  the  functioning  inputting  the  sample  gas.
WARNING !!  From  this  moment  on  for  all  the  duration  of  24  hours  of  self-calibration,  the  probe  must  stay  in
clean  air  without  loss  of  GAS.

The  probe  continues  to  blink  at  a  low  frequency  again  for  24  hours  to  make  sure  that  the  probe  do  the  auto
calibration.

Before  performing  this  operation  disconnect  the  power  to  the  probe

Attention!!
The regulations described in this paragraph must performed be authorized and specialized technician are suceptibile
to compromise the safety of the survey.

If the device does not start up.
Check that the 12/24 Vdc power is present, and that positive and negative polarity has not been inverted.

If the Fault LED lights up.
Check that the cables are connected according to the drawing, and that the wire isolation sheath has not been pinched.
Check the voltage at the terminals 1-2. It must be higher than 10,80 Vdc and lesser than 26,4 Vdc.
Check that  the connector of the  sensor is correctly inserted.

If it’s connected to control unit. Check the voltage at the terminals 2-3. It must be from a minimum of 0.8 Vdc to
a maximum of 1.1 Vdc.

Remark.
If the probes are connected to the control units  BX308 and BX316 the voltage at the terminals 2 and 3 must be from
a minimum of 0.6 to a maximum of 0.75 VDC

If   othe r  p rob le ms  arise ,  a  sp e cialise d   and /or  authorise d   te chnician  and /or  the   Distrib utor  of
BEINAT S.r.l. should be contacted directly.

WARNING.

These  measurement  should  be  performed  in
clean  air.

Moreover,  this  test  must  be  performed  only
with  the  probe  connected  to  a  control  unit,  or
with  a  220  Ohm  resistance  installed  between
terminal  2  and  terminal  3.

.

Troubleshooting before calling a technician

Maintenance  and  gas  sensor  replacement

Probe with sensor                Probe with sensor

            Sensor

      Probe with sensor

to be raplaced

    removed

      remounted

Linear Otput 4-20 mA

3    2    1

R

0

1

3

2

1,1

V.

Vol tmeter

Power Supply
  12÷24 V.

Summary of Contents for SGM600

Page 1: ...mperature environments avoiding false alarms due to anomalous events The probe has a 0 20 LEL linear output conforming to the 4 20mA standard for which can be connected with one of BEINAT s industrial control units The important innovation of this probe is The possibility to substitute the sensor at the end of the operating cycle or fault by the technician without having to send to BEINAT Srl CONF...

Page 2: ...ECTATIONS The installation of the SGM600 Sensor its ordinary and extraordinary maintenance every six months and its out of service removal at the end of the functional life guaranteed by the manufacturer must be carried out by authorized or specialized personnel Do not allow it to become wet The control unit can be seriously damaged as it is not waterproof either when immersed in water or exposed ...

Page 3: ... IP42 1 1 YES NO BX180 unit 1 zone Omega bar DIN 1 IP20 1 1 YES NO BX280 unit 1 zone Omega bar DIN 2 IP20 1 1 YES NO BX449F unit 1 zone Omega bar DIN 4 IP20 1 1 YES NO BX308 unit 1 zone Omega bar DIN 8 IP20 1 1 YES YES BX308 Box unit 1 zone Wall 8 IP65 1 1 YES YES BX316 unit 2 zones Barra Omega 16 IP20 1 2 YES YES BX316 Box unit 2 zones Wall 16 IP65 1 2 YES YES TAKITJ8 Data Collector Wall 8 IP65 M...

Page 4: ...ethane Hydrogen Ammonia Acetylene The probe should not be placed near the appliances to be controlled boilers burners industrial kitchens etc but on the opposite wall The probe should not be affected by smoke vapour etc as they could distort their measurement It must be placed away from sources of heat suction fans ventilation fans Positioning of the Sensor Detectiondiagrams data 30 cm Heavy gases...

Page 5: ...ons 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 ON 1 2 3 4 5 6 K1 K2 K3 Connettore a innesto montato su sonda Led ON connection USB port Selec operation range FUNCTIONING OF LED The integrated LED on the sonde has a threefold function 1 Green LED Normal operation In waiting phase the LED flashes 2 Red LED State of alarm The frequency of light changes according to the percentage of gas monitored 3 Le...

Page 6: ...at the wire isolation sheath has not been pinched Check the voltage at the terminals 1 2 It must be higher than 10 80 Vdc and lesser than 26 4 Vdc Check that the connector of the sensor is correctly inserted If it s connected to control unit Check the voltage at the terminals 2 3 It must be from a minimum of 0 8 Vdc to a maximum of 1 1 Vdc Remark If the probes are connected to the control units BX...

Page 7: ... a sufficient concentration to activate the general alarm Warning If you have the following symptoms vomiting sleepiness or else go to the closest first aid station and inform the operators that you could have been poisoned by Carbon Monoxide or by an excess or deficiency of oxygen NOTES The installation of the SGM600 probe its ordinary and extraordinary maintenance and its out of service removal ...

Page 8: ...UIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable collection point for the recycling of electrical and electronic equipment such as for example sales points in case you buy a new and similar product local collection points waste collection center local recycling center etc By ...

Reviews: