Power Supply   .................................................................................................... 12÷24VDC           ± 10%
Power demand ................................................................. 90 mA in operating, 110 mA in alarm Max @ 13,8 V
Notifications ..................................................... green light normal operation, yellow light fault, red light alarm
Slot exspansion board relay; CARD-03 .......................  Fault , Prealarm, Allarm. Relay contacts 1A 30 VDC  SELV

Sensor    ...............................................................................................................................  Cartalityc
Sensitive element  working  range    ......................................................................................  To  100%  of LEL
Analog output signal  ...................................................................................... 4÷20 mA standard tolerance
Selection of the operating Range ................................................................ from 20% of LEL to 100% of LEL
Detector  accuracy  .....................................................................................................................  1%  FS
Long  term shift in clean air   ...................................................................................................  < 3% of LEL
Auto  zero  procedure    ............................................................................  Included  in  the  software algorithms
Response  Time    ............................................................................................................................  <10”
Warm-up  time  ...................................................................................................................  1,30  minutes

Functioning  humidity    ........................................................................................  0-90%  non  condensed
Functioning  temperature   ............................................................................................  -10°C  to  +60°C
Control units usable ............. BX444-Mc, BX449F, GS100M, BX180, BX280,  BX150, GS300-Mc, BX316xp, BX308xp
Max.  distance  between  probe  and  unit    ..........................................................................................  100  m
Cable  diameter  for  connecting  probe    ..............................................................................................  1  mm
Connection: The cable of connection of the probe must not be installed together with the power cables.
Otherwise, make sure to use a shielded cable
Electromagnetic compatibility  Reference Norms  ............................................................................  EN  50270
Probe’s  body  material    .............................................................................................................  Aluminium
External  degree  of  protection    ........................................................................................................  IP66
Size    .................................................................................................................................  100x100x60

CHECK the integrity of the unit after having removed it from the box.
Check that the data written on the box correspond to the type of gas used.
When doing the electrical connections, follow the drawing closely.
Any use of the detector for purposes other than the intended one is considered improper,
and as a result of which BEINAT S.r.l. therefore disclaims any responsibility for possible
damages caused to people, animals or objects.

TERMS and EXPECTATIONS: The installation of the SGM600  Sensor, its ordinary and
extraordinary maintenance, every six months, and its out of service removal at the end of
the functional life guaranteed by the manufacturer, must be carried out by authorized or
specialized personnel.

Do not allow it to become wet.
The control unit can be seriously damaged as it is not waterproof either when immersed in water or exposed to high
levels of humidity.

Do not drop it.
Heavy knocks or falls during transportation or installation can damage the appliance.

Avoid abrupt temperature fluctuations.
Sudden temperature variations can cause condensation and the control unit could work poorly.

Cleaning
Never clean the device with chemical products. If necessary, wash with a moist cloth.

Precautions

Technical  Specifications

WARNING!
The CATALITIC sensor has a life span of 5 to 6 years in clean air.
The working temperature of the probe recommended is from -10 ° C to + 60 ° C.
Every puffy snapshot of gas over 100% of L.I.E. Takes months off the sensor.
Each immediate puff of gas that exceeds 100% of L.E.L. takes away months of life from the sensor.
The detector must be tested by simulating the presence of gas by issuing it from a pre-calibrated testing aerosol.
Important:
The test of operation and eventually offset cancellation must be performed at least once a year,  by a  qualified
technician.

Code

 

         Type of Gas

                      Sensor

        Working range           Temperature

SGM600met

Methane

Catalytic

LEL 0-100%

-10+60°C

SGM600Agpl

LPG

Catalytic

LEL 0-100%

-10+60°C

SGM600Aidr

Hydrogen

Catalytic

LEL 0-100%

-10+60°C

SGM600Aamm

Ammonia explosiv

Catalytic

LEL 0-100%

-10+60°C

SGM600Aace

Acetylene

Catalytic

LEL 0-100%

-10+60°C

SGM600Avbe

Gasoline vapours

Catalytic

LEL 0-100%

-10+60°C

SGM600Aalc

Alcohol

Catalytic

LEL 0-100%

-10+60°C

Technical Features  SGM600

Summary of Contents for SGM600

Page 1: ...mperature environments avoiding false alarms due to anomalous events The probe has a 0 20 LEL linear output conforming to the 4 20mA standard for which can be connected with one of BEINAT s industrial control units The important innovation of this probe is The possibility to substitute the sensor at the end of the operating cycle or fault by the technician without having to send to BEINAT Srl CONF...

Page 2: ...ECTATIONS The installation of the SGM600 Sensor its ordinary and extraordinary maintenance every six months and its out of service removal at the end of the functional life guaranteed by the manufacturer must be carried out by authorized or specialized personnel Do not allow it to become wet The control unit can be seriously damaged as it is not waterproof either when immersed in water or exposed ...

Page 3: ... IP42 1 1 YES NO BX180 unit 1 zone Omega bar DIN 1 IP20 1 1 YES NO BX280 unit 1 zone Omega bar DIN 2 IP20 1 1 YES NO BX449F unit 1 zone Omega bar DIN 4 IP20 1 1 YES NO BX308 unit 1 zone Omega bar DIN 8 IP20 1 1 YES YES BX308 Box unit 1 zone Wall 8 IP65 1 1 YES YES BX316 unit 2 zones Barra Omega 16 IP20 1 2 YES YES BX316 Box unit 2 zones Wall 16 IP65 1 2 YES YES TAKITJ8 Data Collector Wall 8 IP65 M...

Page 4: ...ethane Hydrogen Ammonia Acetylene The probe should not be placed near the appliances to be controlled boilers burners industrial kitchens etc but on the opposite wall The probe should not be affected by smoke vapour etc as they could distort their measurement It must be placed away from sources of heat suction fans ventilation fans Positioning of the Sensor Detectiondiagrams data 30 cm Heavy gases...

Page 5: ...ons 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 ON 1 2 3 4 5 6 K1 K2 K3 Connettore a innesto montato su sonda Led ON connection USB port Selec operation range FUNCTIONING OF LED The integrated LED on the sonde has a threefold function 1 Green LED Normal operation In waiting phase the LED flashes 2 Red LED State of alarm The frequency of light changes according to the percentage of gas monitored 3 Le...

Page 6: ...at the wire isolation sheath has not been pinched Check the voltage at the terminals 1 2 It must be higher than 10 80 Vdc and lesser than 26 4 Vdc Check that the connector of the sensor is correctly inserted If it s connected to control unit Check the voltage at the terminals 2 3 It must be from a minimum of 0 8 Vdc to a maximum of 1 1 Vdc Remark If the probes are connected to the control units BX...

Page 7: ... a sufficient concentration to activate the general alarm Warning If you have the following symptoms vomiting sleepiness or else go to the closest first aid station and inform the operators that you could have been poisoned by Carbon Monoxide or by an excess or deficiency of oxygen NOTES The installation of the SGM600 probe its ordinary and extraordinary maintenance and its out of service removal ...

Page 8: ...UIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable collection point for the recycling of electrical and electronic equipment such as for example sales points in case you buy a new and similar product local collection points waste collection center local recycling center etc By ...