If the device does not start up.
Check that the 12/24 Vdc power is present, and that positive and
negative polarity has not been inverted.
If the Fault LED lights up.
If the fault signal reaches the control unit connected to the probe.
Check that the cables are connected according to the drawing, and
that the wire isolation sheath has not been pinched.
Ch eck.
heck the voltage at the terminals 2-3. It must be from a minimum
of 0.8 Vdc to a maximum of 1.1 VDC.
.
Check
That six years have elapsed from the installation date
ATTENTION.
These measurement should be performed in clean air.
Moreover, this test must be performed only with the probe connected to a control unit, or with a 220 Ohm
resistance installed between terminal 2 and terminal 3..
If othe r p rob le ms arise , a sp e cialise d and /or authorise d te chnician and /or the Distrib utor of
Beinat s.r.l. should be contacted directly.
Maintenance Troubleshooting before calling a technician
The overall testing and the ordinary or extraordinary maintenance It must be carried out every six months by
emitting gas from a pre-calibrated bottle within the percentages of test plate of the probe.
To perform a perfect test. connect the tester TS1008 to the USB port and emit the agas from the
precalibrated bottle
GA S
te st
Attention: The settings described in this paragraph must performed by qualified personal as such these
settings are susceptible to compromise safety of detection.
IMPORTANT: Do not open the transmitter when energized.
The installation of the detector does not exempt from ..... The compliance with all regulations concerning the characteristics,
installation and use of gas appliances. The ventilation of the spaces and the elimination of combustion products are described
in the UNI norms according to ART. 3 LAW 1083 / 71 and relevant legal provisions.
GAS
Without gas it reads 0% of Gas With gas it reads the % detected