Technical specifications

CHECK  the  integrity  of  the  probe  after  having  removed  it  from  the  box.
Check that the data written on the box correspond to the type of gas used.
When doing the electrical connections, follow the drawing closely.
Any use of the detector for purposes other than the intended one is considered improper, and as a result of which BEINAT
S.r.l. 
 therefore disclaims any responsibility for possible damages caused to people, animals or objects.
LIABILITY LIMITATIONS
* BEINAT S.R.L.
 cannot be held liable to any person in regard to material damages, injuries or death of the user resulting
entirely or partially from misuse, wrong installation or storage of the product non conforming with the instructions and
warnings and/or non conforming with the norms and regulations in force.
* BEINAT S.R.L. does not support nor authorizes any other company, person or legal entity to take on the part of
responsibility assigned to BEINAT S.R.L., even if involved in the sale of the products of BEINAT S.R.L.
* BEINAT S.R.L.
 shall not be held liable for the direct or indirect damages, as well as for the compensation of direct
or indirect damages, resulting from the sale and use of its products, WHEN SUCH PRODUCTS WERE NOT SPECIFIED AND
ALLOWED BY BEINAT S.R.L. FOR A SPECIFIC USAGE.
INSTALLATION
When performing the installation, please remind that if you pierce the FLAMEPROOF container, it will lose its properties
and its conformity to REGULATIONS.
TERMS and EXPECTATIONS: The installation of the SG895 probe, its ordinary and extraordinary maintenance, and
its out of service removal at the end of the functional life guaranteed by the manufacturer, must be carried out by
authorized and/or specialized personnel.
Do not allow it to become wet.
The probe can be seriously damaged when immersed in water. Remember that the probe has an EEX protection degree.
Do not drop it.
Heavy knocks or falls during transportation or installation can damage the appliance.
Avoid abrupt temperature fluctuations.
Sudden temperature variations can cause condensation and the probe could work poorly.
Cleaning
Never clean the device with chemical products. If necessary, wash with a moist cloth.
Absolutely avoid using any cloth dipped in thinners, alcohol and chemical detergents.

Power supply ..................................................................................................... 12÷24 VDC         ± 10%
Power demand  .................................................................. 90 mA in function, 100 mA in alarm Max @ 13.8V

Sensor II 2 G EEx d II C Directive ATEX 94/9/CE   ...............................................  Catalytic/Electrochemical  cell
Sensitive element working range  refered explsive gas ......................................................... At 100% of L.E.L.
Sensitive element working range  refered toxic  gas .................................................................. At 1000 ppm
Detector’s range of measurement according to the type of gas .......................................... See table on page 4
Detector  accuracy  .....................................................................................................................  1%  FS
Long  term shift in clean air   ................................................................................................  < 3% of L.E.L.
Response  Time    ...........................................................................................................................  <  10”
Auto zero procedure  .............................................................................  Included in the software algorithms
Waiting time (warm-up time) ...................................................................................................... 4 minutes
Slot exspansion board relay; CARD-03 .......................  Fault , Prealarm, Allarm. Relay contacts 1A 30 VDC  SELV

Analog  output  signal   ...............................................................................  4÷20  mA  standard  tolerance
Functioning humidity  ................................................................................................. 0-90% non condensed
Functioning temperature  refered explsive gas  ........................................................................  -10+70°C
Functioning  temperature  refered  toxic    gas  ............................................................................  -20+50°C
Temperatura di stoccaggio  ..........................................................................................................-25+70°C

Control  units  that  can  be  used  ...  BX444-Mc,  BX449/F,  GS100M,  BX180,  BX280,    BX150,  GS300
M,  BX316,  BX308
Max.  distance  between  probe  and  unit    .......................................................................................  100  m
Cable  diameter  for  connecting  probe    .........................................................................................  1  mm
Connection:  The  cable  of  connection  of  the  probe  must  not  be  installed  together  with  the  power
cables. Otherwise, make sure to use a shielded cable
Case  ......................................................................................  ATEX  IIGD  EEx-d  T6  CES  I  03  ATEX148
Probe’s  body  material    ............................................................................................  Die-cast  aluminium
Protection  ...................................................................................................................................  IP66
Dimensions  (probe’s  body diameter)  ...................................................................................... 100  mm
External degree of protection

 ..................................................... ATEX IIGD EEx-d T6 CES I 03 ATEX148

Precautions

MAINTENANCE

The user periodically (every 6 months) must perform a check of the operation of the control unit by spraying

a suitable test gas at the base of the probes connected until the alarm condition is reached.

• At least once a year make a more accurate check by a specialist technician.

• Disabling the detector must be carried out by qualified personnel.

Summary of Contents for SG895

Page 1: ...the home fitness concept The device has the capacity of controlling through its Catalytic technology sensors the presence of Explosive Gases TOXIC GAS such as Carbon Monoxide see table on page 5 Thanks to its innovative technology advances the probe is suitable to industrial use and car parks The probe is managed by a microprocessor which not only supplies an alarm signal to the Control Unit conne...

Page 2: ...ation or installation can damage the appliance Avoid abrupt temperature fluctuations Sudden temperature variations can cause condensation and the probe could work poorly Cleaning Never clean the device with chemical products If necessary wash with a moist cloth Absolutely avoid using any cloth dipped in thinners alcohol and chemical detergents Power supply 12 24 VDC 10 Power demand 90 mA in functi...

Page 3: ...ould be grounded and connected to the external or internal terminal that must be protected against corrosion The user should regularly clean the product in order to avoid any dust accumulation on its walls The sensors should be installed mechanically so that the detection cell is facing down If the connections are located in a classified zone they should be protected in certified cases 65 mm 100 m...

Page 4: ...m the highest point of the ceiling in order to detect Volatil gases CO The probe should not be installed near the appliance to be controlled but on the opposite wall The probe should not be affected by smoke vapour etc as they could distort its measurement It should be located away from sources of heat ventilators or fans Technical specifications of the gas detection capsules Positioning ofthe pro...

Page 5: ...abling Please read the paragraph Particular Specifications for Use in Explosive Atmospheres in conformance with the European Directive ATEX 2014 34 UE NOTE Please remind that if you pierce the FLAMEPROOF container it will completely lose its properties Moreover you should install a FLAMEPROOF cable gland for the connection cables Selec operating range Led ON connection USB port Led ON connection U...

Page 6: ...m A Linear 5 Fault Zone 9 3 12 14 6 17 3 Output in mA Clean Air 300 ppm CO 100 ppm CO 50 ppm CO 30 ppm CO Time in minutes Diagram detection time mA Referred to the CO gas Current Voltage Conversion Graph with 220 Ohm Load Resistance 0 4 5 10 15 20 V m A 0 88 1 1 2 2 3 3 4 4 Linear 5 0 50 100 150 200 250 10 Toxic Gas Detection diagram Warning for gas chlorine range 0 10 ppm PowerSupply 12 24 V Line...

Page 7: ... of Beinat s r l should be contacted directly Maintenance Troubleshooting before calling a technician The overall testing and the ordinary or extraordinary maintenance It must be carried out every six months by emitting gas from a pre calibrated bottle within the percentages of test plate of the probe To perform a perfect test connect the tester TS1008 to the USB port and emit the agas from the pr...

Page 8: ...al city office your household waste disposal service or the shop where you purchased the product Attention in some countries of the European Union the product is not included in the field of application of the National Law that applies the European Directive 2002 96 EC and therefore these countries have no obligation to carry out a separate collection at the end of life of the product WARRANTY The...