The  installation  of  the  SGM595  probe,  its  ordinary  and
extraordinary  maintenance,  and  its  out  of  service  removal
at  the  end  of  the  functional  life  guaranteed  by  the
manufacturer,  must  be  carried  out  by  authorized  or
specialized  personnel.

The  general  test  should  be  performed  by  issuing  gas  from
a  pre-calibrated  aerosol  within  the  percentages  illustrated
on  the  side.

Important: 

This  test  must  be  carried  out  at  least  once  a

year.

Gas  imput  Test

WARNING! Actions to be taken in case of alarm

Gas
1) P
ut out all free flames.
2) Close the main gas tap or the LPG cylinder tap.
3) Do not turn any lights on or off; do not turn on any electrical device or appliance.
4) Open windows and doors in order to increase ventilation.
If the alarm stops, its cause must be found and the relevant consequent measures taken.
If the alarm continues and the cause of gas presence cannot be found or removed, abandon the building and call
the emergency services when outside (fire department, distributors, etc.)

IMPORTANT:  The  operation  test  should  not  be  carried  out  with  the  gas  tap  as  this  does  not  guarantee  a  sufficient
concentration  to  activate  the  general  alarm.

Warning !!

If you have the following symptoms: vomiting, sleepiness, or else, go to the closest first aid station
and inform the operators that you could have been poisoned by Carbon Monoxide

or by an excess

or  deficiency  of  oxygen

N O T E S

Gas

SG580  Test

Methane

At 20% of L.E.L. ±2%

LPG

At 20% of L.E.L. ±2%

Hydrogen

At 20% of L.E.L. ±2%

Summary of Contents for SG580

Page 1: ...CONFORMITY Installation and user guide Important Assembly maintenance of the appliance must be carried out by qualified personnel and in accordance with applicable laws and regulations The manufacturer assumes no responsibility for the use of products that have to comply with particular environmental and or installation standards Important note Before connecting the equipment it is recommended tha...

Page 2: ...on of the SG580Sensor its ordinary and extraordinary maintenance every six months and its out of service removal at the end of the functional life guaranteed by the manufacturer must be carried out by authorized or specialized personnel Do not allow it to become wet The control unit can be seriously damaged as it is not waterproof either when immersed in water or exposed to high levels of humidity...

Page 3: ...unit 1 zone Panel 1 IP42 1 1 YES NO BX180 unit 1 zone Omega bar DIN 1 IP20 1 1 YES NO BX280 unit 1 zone Omega bar DIN 2 IP20 1 1 YES NO BX449F unit 1 zone Omega bar DIN 4 IP20 1 1 YES NO BX308 unit 1 zone Omega bar DIN 8 IP20 1 1 YES YES BX308 Box unit 1 zone Wall 8 IP65 1 1 YES YES BX316 unit 2 zones Barra Omega 16 IP20 1 2 YES YES BX316 Box unit 2 zones Wall 16 IP65 1 2 YES YES TAKITJ8 Data Coll...

Page 4: ...etylene The probe should not be placed near the appliances to be controlled boilers burners industrial kitchens etc but on the opposite wall The probe should not be affected by smoke vapour etc as they could distort their measurement It must be placed away from sources of heat suction fans ventilation fans Positioning of the Sensor Detectiondiagrams data ppm 0 50 100 150 200 250 300 6 7 Toxic Gas ...

Page 5: ... the operating range to 100 LEL you need to move the jumper between the central and the top pole Electrical cabling Please read the paragraph Particular Specifications for Use in Explosive Atmospheres NOTE Please remind that if you pierce the FLAMEPROOF container it will completely lose its properties Moreover you should install a FLAMEPROOF cable gland for the connection cables 3 2 1 1 2 3 4 5 6 ...

Page 6: ...not been pinched Check the voltage at the terminals 1 2 It must be higher than 10 80 Vdc and lesser than 26 4 Vdc Check that the connector of the sensor is correctly inserted If it s connected to control unit Check the voltage at the terminals 2 3 It must be from a minimum of 0 8 Vdc to a maximum of 1 1 Vdc Remark If the probes are connected to the control units BX308 and BX316 the voltage at the ...

Page 7: ...electrical device or appliance 4 Open windows and doors in order to increase ventilation If the alarm stops its cause must be found and the relevant consequent measures taken If the alarm continues and the cause of gas presence cannot be found or removed abandon the building and call the emergency services when outside fire department distributors etc IMPORTANT The operation test should not be car...

Page 8: ...l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable collection point for the recycling of electr...

Reviews: