BEINAT SG580 Installation And User Manual Download Page 2

Page  2

Power Supply   .................................................................................................... 12÷24VDC           ± 10%
Power demand ................................................................. 90 mA in operating, 110 mA in alarm Max @ 13,8 V
Notifications ..................................................... green light normal operation, yellow light fault, red light alarm
Slot exspansion board relay; CARD-03 .......................  Fault , Prealarm, Allarm. Relay contacts 1A 30 VDC  SELV

Sensor    ...............................................................................................................................  Cartalityc
Sensitive element  working  range    ......................................................................................  To  100%  of LEL
Analog output signal  ...................................................................................... 4÷20 mA standard tolerance
Selection of the operating Range ................................................................ from 20% of LEL to 100% of LEL
Detector  accuracy  .....................................................................................................................  1%  FS
Long  term shift in clean air   ...................................................................................................  < 3% of LEL
Auto  zero  procedure    ............................................................................  Included  in  the  software algorithms
Response  Time    ............................................................................................................................  <10”
Warm-up  time  ...................................................................................................................  1,30  minutes

Functioning  humidity    ........................................................................................  0-90%  non  condensed
Functioning  temperature    ............................................................................................  -10°C  to  +50°C
Control units usable ............. BX444-Mc, BX449F, GS100M, BX180, BX280,  BX150, GS300-Mc, BX316xp, BX308xp
Max.  distance  between  probe  and  unit    ..........................................................................................  100  m
Cable  diameter  for  connecting  probe    ..............................................................................................  1  mm
Connection: The cable of connection of the probe must not be installed together with the power cables.
Otherwise, make sure to use a shielded cable
Probe’s  body  material    ............................................................................................................  Alluminium
External  degree  of  protection    .....................................................................................  Antideflagrate  IP66
Size    ......................................................................................................................................  100  mm

CHECK the integrity of the unit after having removed it from the box.
Check that the data written on the box correspond to the type of gas used.
When doing the electrical connections, follow the drawing closely.
Any use of the detector for purposes other than the intended one is considered improper, and
as a result of which BEINAT S.r.l. therefore disclaims any responsibility for possible damages
caused to people, animals or objects.

TERMS and EXPECTATIONS: The installation of the SG580 Sensor, its ordinary and extraordinary
maintenance, every six months, and its out of service removal at the end of the functional life
guaranteed by the manufacturer, must be carried out by authorized or specialized personnel.

Do not allow it to become wet.
The control unit can be seriously damaged as it is not waterproof either when immersed in water or exposed to high
levels of humidity.

Do not drop it.
Heavy knocks or falls during transportation or installation can damage the appliance.

Avoid abrupt temperature fluctuations.
Sudden temperature variations can cause condensation and the control unit could work poorly.

Cleaning
Never clean the device with chemical products. If necessary, wash with a moist cloth.

Precautions

Technical  Specifications

WARNING!
The CATALITIC sensor has a life span of 5 to 6 years in clean air.
The working temperature of the probe recommended is from -10 ° C to + 50 ° C.
Every puffy snapshot of gas over 100% of L.I.E. Takes months off the sensor.
Each immediate puff of gas that exceeds 100% of L.E.L. takes away months of life from the sensor.
The detector must be tested by simulating the presence of gas by issuing it from a pre-calibrated testing aerosol.
Important:
The test of operation and eventually offset cancellation must be performed at least once a year,  by a  qualified
technician.

Code

 

         Type of Gas

                      Sensor

        Working range           Temperature

SGM595/Amet

Methane

Catalytic

LEL 0-100%

-10+50°C

SGM595/Agpl

LPG

Catalytic

LEL 0-100%

-10+50°C

SGM595/Aidr

Hydrogen

Catalytic

LEL 0-100%

-10+50°C

SGM595/Aamm

Ammonia explosiv

Catalytic

LEL 0-100%

-10+50°C

SGM595/Aace

Acetylene

Catalytic

LEL 0-100%

-10+50°C

SGM595/Avbe

Gasoline vapours

Catalytic

LEL 0-100%

-10+50°C

SGM595/Aalc

Alcohol

Catalytic

LEL 0-100%

-10+50°C

Technical Features  SG580

Summary of Contents for SG580

Page 1: ...CONFORMITY Installation and user guide Important Assembly maintenance of the appliance must be carried out by qualified personnel and in accordance with applicable laws and regulations The manufacturer assumes no responsibility for the use of products that have to comply with particular environmental and or installation standards Important note Before connecting the equipment it is recommended tha...

Page 2: ...on of the SG580Sensor its ordinary and extraordinary maintenance every six months and its out of service removal at the end of the functional life guaranteed by the manufacturer must be carried out by authorized or specialized personnel Do not allow it to become wet The control unit can be seriously damaged as it is not waterproof either when immersed in water or exposed to high levels of humidity...

Page 3: ...unit 1 zone Panel 1 IP42 1 1 YES NO BX180 unit 1 zone Omega bar DIN 1 IP20 1 1 YES NO BX280 unit 1 zone Omega bar DIN 2 IP20 1 1 YES NO BX449F unit 1 zone Omega bar DIN 4 IP20 1 1 YES NO BX308 unit 1 zone Omega bar DIN 8 IP20 1 1 YES YES BX308 Box unit 1 zone Wall 8 IP65 1 1 YES YES BX316 unit 2 zones Barra Omega 16 IP20 1 2 YES YES BX316 Box unit 2 zones Wall 16 IP65 1 2 YES YES TAKITJ8 Data Coll...

Page 4: ...etylene The probe should not be placed near the appliances to be controlled boilers burners industrial kitchens etc but on the opposite wall The probe should not be affected by smoke vapour etc as they could distort their measurement It must be placed away from sources of heat suction fans ventilation fans Positioning of the Sensor Detectiondiagrams data ppm 0 50 100 150 200 250 300 6 7 Toxic Gas ...

Page 5: ... the operating range to 100 LEL you need to move the jumper between the central and the top pole Electrical cabling Please read the paragraph Particular Specifications for Use in Explosive Atmospheres NOTE Please remind that if you pierce the FLAMEPROOF container it will completely lose its properties Moreover you should install a FLAMEPROOF cable gland for the connection cables 3 2 1 1 2 3 4 5 6 ...

Page 6: ...not been pinched Check the voltage at the terminals 1 2 It must be higher than 10 80 Vdc and lesser than 26 4 Vdc Check that the connector of the sensor is correctly inserted If it s connected to control unit Check the voltage at the terminals 2 3 It must be from a minimum of 0 8 Vdc to a maximum of 1 1 Vdc Remark If the probes are connected to the control units BX308 and BX316 the voltage at the ...

Page 7: ...electrical device or appliance 4 Open windows and doors in order to increase ventilation If the alarm stops its cause must be found and the relevant consequent measures taken If the alarm continues and the cause of gas presence cannot be found or removed abandon the building and call the emergency services when outside fire department distributors etc IMPORTANT The operation test should not be car...

Page 8: ...l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable collection point for the recycling of electr...