User Guide Revision 1.12
4
IP20 Quick Start Up Guide
AC Supply Connection
Supply Voltage
3 Phase Units : Connect L1 L2 L3, PE
200 – 240 Volts + / - 10%
1 Phase Units : Connect L1, L2, PE
380 – 380 Volts + / - 10%
Fuses or MCB
o
Check the Drive Rating Information in section 13.4
Help Card
Display
Information can be found in section 5.1
Keypad Operation
can be found in section 5.1
IMPORTANT!
Hardware Enable
Link the terminals as shown, optionally through switch contacts to enable
drive operation
Control Terminals
Based on the factory default parameter settings
Run – Stop
10K Speed Pot
Close the switch to run (enable), open to stop
Motor Cable
o
For correct cable size in section 13.4
o
Observe the maximum permissible motor cable length
o
For Motor cable lengths > 50 metres, an output filter is
recommended
o
Use a screened (shielded cable)
Motor Connection
o
Check for Star or Delta connection according to the motor
voltage rating in section 4.5.
o
Motor Nameplate Details
o
Motor Rated Voltage : P1-07
o
Motor Rated Current : P1-08
o
Motor Rated Frequency : P1-09
o
Motor Rated Speed (Optional) : P1-10