Technical Data

Parameter

EXTER T150

Front panel, W x H x D

398 x 304 x 6 mm

Mounting depth

60 mm (160 mm including clearance)

Front panel seal

IP 66

Rear panel seal

IP 20

Keyboard
material/Front
panel

Touch screen: Polyester on glass, 1 million

fi

nger touch

operations. Overlay: Autotex F157 or F207*.

Reverse side
material

Powder-coated aluminum

Weight

3.7 kg

Serial port
RS422/RS485

25-pin D-sub contact, chassis-mounted female with
standard locking screws 4-40 UNC

Serial port RS232C

9-pin D-sub contact, male with standard locking screws 4-40
UNC

Flash memory for
application

12 MB (incl. fonts)

Ethernet

Shielded RJ 45

USB

Host type A (USB 1.1), max output current 500 mA
Device type B (USB 1.1)

CF-slot

Compact

fl

ash, type I and II

Real time clock

±20 PPM + error because of ambient temperature. Total
maximum error: 1 minute/month at 25 °C.
Temperature coef

fi

cient: -0.034±0.006 ppm/°C

2

Real time clock
battery

CR2450 (UL and cUL: Sanyo or Panasonic)
Minimum lifetime: 3 years

Power consumption
at rated voltage

Normal: 1.2 A
Maximum: 1.7 A

Display

TFT-LCD, 1024 x 768 pixels, 64K colors.
LED backlight lifetime at the ambient temperature of
+25 °C: >50,000 h.

Active area of
display, W x H

304.1 x 228.1 mm

Fuse

Internal DC fuse, 3.15 AT, 5 x 20 mm

Power supply

+24 V DC (20 - 30 V DC). Power supply connector.
CE: The power supply must conform with the requirements
according to IEC 60950 and IEC 61558-2-4.
UL and cUL: The power supply must conform with the
requirements for class II power supplies.

Ambient
temperature

Vertical installation: 0 ° to +50 °C
Horizontal installation: 0 ° to +40 °C

Storage temperature

-20 ° to +70 °C

Beijer Electronics, MAEN775E

11

Summary of Contents for EXTER T150

Page 1: ...EXTER T150 Installation Manual English MAEN775E 2014 11...

Page 2: ...updating this publication Beijer Electronics AB assumes no responsibility for any errors that may appear in this document Read theentireinstallation manual prior to installing and using this equipment...

Page 3: ...10 3 TechnicalData 11 4 ChemicalResistance 13 4 1 MetalCasing 13 4 2 Touch Screen and Overlay Material 13 4 2 1 Autotex F157 207 13 4 2 2 Touch Screen Surface 14 4 2 3 Touch Screen Protector 15 5 Ope...

Page 4: ...sa powerful irritant Incase of skincontact wash immediately with plenty ofwater In case of eye contact holdthe eye open ush with plenty of water and get medical attention The gures in this manualserve...

Page 5: ...This product contains a battery this must onlybe changedin an areaknown tobe non hazardous Replace the battery with aCR2450 battery Use of anothertype ofbattery maypresent a risk of re orexplosion Wa...

Page 6: ...oweroutlet Peripheral equipment must be appropriate forthe application and location 1 4 During Use Keep the operatorpanel clean Emergency stopand othersafety functions may notbe controlled from the op...

Page 7: ...0 inch 50 mm 2 0 inch 11 97 inch 15 67 inch 2 36 inch Caution The openings on the enclosure are for airconvection Do not cover these openings 2 2 Installation Process 1 Unpackand check the delivery If...

Page 8: ...operator panelistobe situated draw along the outer sides ofthe holesandcutaccording to the markings 3 Secure the operator panel in position usingallthe fasteningholesand the provided brackets and scre...

Page 9: ...rrors in communication may occur Ensure that the voltage and polarity of the powersource is correct Separate high voltage cables from signal and supply cables Shielded communication cables are recomme...

Page 10: ...the Controller For information aboutthe cables to be used when connecting the operator panelto the controller please refer to the help le for thedriverin question 2 2 3 Other Connections and Periphera...

Page 11: ...pact flash type I and II Real time clock 20 PPM error because of ambient temperature Total maximum error 1 minute month at 25 C Temperature coefficient 0 034 0 006 ppm C2 Real time clock battery CR245...

Page 12: ...XTER T150 Relative humidity 5 85 non condensed Approvals and certifications Information is available on the web site www beijerelectronics com See section ChemicalResistance for more information Beije...

Page 13: ...Hydrochloric acid 5 Nitric acid 10 Isopropyl alcohol Phosphoric acid 43 Na hypochlorite 10 Turpentine Note If exposure to any of the above chemicals is demanded itis recommended to first test the chem...

Page 14: ...l Windex1 Cyclohexanol Persil powderin solution1 Wisk Diacetone alcohol Petroleum spirit1 1 Extremely faintglossingof the texture was noted Autotex withstands DIN 42 115 Part2 exposure of up to 1 hour...

Page 15: ...een Protector For harsh environments and exposure tooutdoorconditions it isrecommended to use a protective lm toguardthe touch screenfromdamage These optional parts can be ordered from Beijer Electron...

Page 16: ...Operator PanelDrawings 5 Operator Panel Drawings 5 1 Communication Ports RS 232 RS 422 RS 422 485 RS 485 Ethernet USB Beijer Electronics MAEN775E 16...

Page 17: ...Operator PanelDrawings 5 2 EXTER T150 Outline Beijer Electronics MAEN775E 17...

Page 18: ...aid between the panel s chassis and the closest groundingpoint on the door see 3 in drawingabove 3 Connect astrongbut shortgroundingbraid betweenthe doorand the device cabinet see 4 indrawingabove 4 T...

Page 19: ...nithas its shield directly grounded or groundedviaa capacitor Note In many cases connecting the shielded Ethernet cabling to the chassis at both ends is inappropriate Hum or grounding loops canoccur U...

Page 20: ...e shield to the ground via a 0 1 F 250 Vplastic capacitor Both ends are then connected tothe ground in terms ofHF but only connected to the ground at one end in terms ofLF thus avoidingthe 50 Hz groun...

Page 21: ...a large program for controllingthe temperature in the device cabinet An enamel coated steel cabinethasaradiant heatvalue of 5 5 W m2 and degrees C Installinga fan inside the cabinetwill even out the...

Page 22: ...LVaccording to EN 60950 protection against electric shock andUL 950 Note Here is an example that explains why a secure 24 V DC feed can be ruined by mixing 24 V relay contacts with 230 V AC relay cont...

Page 23: ...SB memory stick keyboard or similardevice is plugged in If anumberofunitsare connectedthat have a0 Vand a groundconnection and these are connected to various groundingpoints there is a substantial ris...

Page 24: ...ires may be onthe same levelor require pull up orpull downtoensure that no faultysignals are detected when the busisin restingmode all transmittersare disconnected 1 2 3 4 5 V 0 V 1 K 1 K 120 ohm 120...

Page 25: ...Head office Beijer Electronics AB Box 426 201 24 Malm Sweden www beijerelectronics com 46 40 358600...

Reviews: