Additional Installation Tips
Note:
The grounding wires should be short and the conductor should have a large area.
A long, thin grounding wire has a very high impedance (resistance) at high frequencies
and does not guide disturbances to the ground.
Multi-wire conductors are better than single wire conductors with the same area.
A braided conductor wire with the same area is even better. The best is a short, thick
grounding braid.
6.2 Ethernet Connection in the
Operator Panel
1
2
3
4
5
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
Industrial Ethernet
Operator panel
Operator panel
Operator panel
Operator panel
Shielded
Short and
unshielded
0.1
μ
F
250 V
1-1
3-3
8-8
2-2
In some industrial units for Ethernet, the RJ45 contact’s shield is connected to the
chassis via a capacitor, see 1 in drawing above.
The operator panel’s Ethernet shield is directly connected to the chassis, see 2 in
drawing above.
1. Check whether the other Ethernet unit has its shield directly grounded or
grounded via a capacitor.
Note:
In many cases, connecting the shielded Ethernet cabling to the chassis at both ends is
inappropriate. Hum or grounding loops can occur. Unshielded cabling may even result
in fewer communication errors.
22
Beijer Electronics, MAEN274
Summary of Contents for BoX2 extreme
Page 1: ...BoX2 base Installation Manual English MAEN274 2018 03...
Page 2: ......
Page 4: ...Foreword Beijer Electronics MAEN274...
Page 6: ...Contents Beijer Electronics MAEN274...
Page 14: ...Installation 14 Beijer Electronics MAEN274...
Page 16: ...Technical Data 16 Beijer Electronics MAEN274...
Page 18: ...Chemical Resistance 18 Beijer Electronics MAEN274...