6.1 Monitoring from Keypad
Put P14=201 to access monitor values in parameter group P0.
Par
Description
Display range Explanation
P0-01
1st Analog Input Value
0 … 100%
100% = max input voltage
P0-02
2nd Analog Input Value
0 … 100%
100% = max input voltage
P0-03
Speed Reference Input
-P-01 … P-01
Displayed in Hz if P-10 = 0, otherwise displayed in RPM
P0-04
Digital Input Status
Binary value
Drive digital input status
P0-05
User PI output (%)
0 … 100%
User PI output (%)
P0-06
DC bus ripple (V)
0 … 100%
DC bus ripple (V)
P0-07
Applied Motor Voltage
0 … 600V AC
Value of RMS voltage applied to motor
P0-08
DC Bus Voltage
0 … 1000V dc
Internal DC bus voltage
P0-09
Heatsink temperature
-20 … 120 °C
Temperature of heatsink in ᵒC
P0-10
Hours Run Meter
0 to 99 999 hours
Not affected by resetting factory default parameters
P0-11
Run Time Since Last Trip1
0 to 99 999 hours
Run-time clock stopped by drive disable or trip.
P0-12
Run Time Since Last Trip2
0 to 99 999 hours
Run-time clock stopped by drive disable or trip. Not reseted
by power down / power up cycling.
P0-13
Trip Log
0 to 99 999 hours
Displays most recent 4 trips with time stamp
P0-15
DC Bus Voltage Log
0 … 1000V
8 most recent values prior to trip, updated every 256ms
P0-16
Heatsink Temperature Log
-20 … 120 °C
8 most recent values prior to trip, updated every 30s
P0-17
Motor Current
0 to 2x rated current 8 most recent values prior to trip, updated every 256ms
P0-18
DC bus ripple log (V)
0 … 100%
8 most recent values prior to trip, 22ms sample time
P0-19
Internal drive temperature log
-20 … 120 °C
8 most recent values prior to trip, 30 s sample time
P0-20
Internal drive temperature
-20 … 120 °C
Actual internal ambient temperature in ᵒC
P0-23
Temperature log cooling fin
Hours:min
Total time of operation above heatsink temp of 85ᵒC
P0-24
Temperatur log internally
Hours:min
Total time of operation with drive internal temperatur above
80ᵒC
P0-25
Estimated rotor speed
0 … 500 Hz
In vector control modes, estimated rotor speed in Hz
P0-26
kWh meter / MWh meter
0.0 kWh / 0 MWh
Total number of kWh / MWh consumed by the drive.
P0-27
Total run time of drive fans
Hours:min:sec
First value displays time in hrs, press up to display mm:ss.
P0-28
Software version
e.g. “1.00”, “47AE”
“1”: Indicates I/O processor, “2“ : Indicates power stage
P0-29
Drive type identifier
BFI type, Drive rating, input phases, voltage, firmware
P0-30
Drive serial number
xxxxxx / yy / zzz
Unique drive serial number
P0-31
Motor current Id / Iq
0 to 2x rated current Displays magnetising current (Id) and torque current (Iq).
P0-32
Actual PWM switching
frequency (kHz)
4 to 32 kHz
Actual switching frequency used by drive
P0-33
Critical fault counter – O-I
Number of times
Number of trips due to overcurrent
P0-34
Critical fault counter – O-Volts
Number of times
Number of trips due to over voltage
P0-35
Critical fault counter – U-Volts
Number of times
Number of trips due to under voltage
P0-36
Critical fault counter – O-temp
Number of times
Number of trips due to over temperature heatsink
P0-38
Error counter – O-hEAt
Number of times
Number of trips due to internal over temperature
P0-39
Error counter – Modbus
Number of times
Number of trips due to Modbus error
P0-47
Fire mode running Hours
Hours
Number of Hours in Fire mode
P0-48
Scope channel 1 & 2
Displays value for Scope channel 1 & 2
P0-49
Scope channel 3 & 4
Displays value for Scope channel 3 & 4
P0-50
Bootloader and motor control
Internal value