6
SPECIFICATIONS
Determine Rotary Field Direction
3 phase indication
Via LEDs
Indication of phase rotation
Via LEDs
Voltage range (Ume)
100…700 V AC phase to phase
Frequency range (fn)
16…400 Hz
Indicaton for false input voltage
difference of > ±30% between the
phase to phase voltages
(> ± 65% between phase to neutral
voltages)
Nominal test current (In in per phase)
< 3.5 mA
General Specifications
Operating time
Continuous
Operating temperature
0
O
C to 40
O
C (32
O
F to 104
O
F)
Operating altitude
Up to 2000 m
Humidity (Without condensation)
≤
80% RH
Storage conditions
0
O
C to 40
O
C (32
O
F to 104
O
F),
≤
80% RH
Power supply
From unit under test
Dust/water resistance
IP 40
Pollution degree
2
Dimensions (H x W x D)
137 x 65 x 33 mm (5.43 x 2.56 x 1.3 in)
Weight
253 g (0.56 lb) with test leads
Product Standard
EN 61557 -1/-7
Electrical safety
EN 61010-1, EN 61557-7
Overvoltage category
CAT IV 600 V
EMC
Conforms to EN 61326-1
Agency approvals
P