background image

Figure 1

Figure 5

Figure 6

Figure 7

Figure 8

Figure 10

Figure 9

120-347 VAC

LED LIGHT

SOURCE

BATTERY

+

-

+

-

L (black)
N (neutral)
G (green)

LED LIGHT

SOURCE

LED SIGN

(red connector)

926000229

Figure 2

Figure 3

Figure 4

Loop lock

AC/LED 
wires

Tie pad

Tie wrap

Bump

Notch

Plastic
Bushing

Swing to vertical
position

Tie pad

Max. mounting height is 14.5 ft to get an 
average illuminance above 1 fc, based on 
3x3 ft room 80/50/20 reflectance.

Base assembly

Base

Cover

TROUBLESHOOTING 

EXIT SIGN DOES NOT COME ON AT ALL
1.   Check AC supply and all AC connections - be sure sign has 24 hour AC supply (unswitched).
2.   Check supply voltage and AC connections. The AC supply must be at least 80% of nominal (96V on a 120V line)
 

for equipment to function normally. At lower voltages the LEDs will begin to glow dimly until the source voltage

 

drops below the full “turn-on” point.

NOTE:  This condition may also be caused by incorrectly connecting a 120 Volt supply line to the
 

 

capacitor assembly lead.

3.   AC supply is OK; replace LED circuit board assembly

MAINTENANCE

 

1. The lamps listed herein when used according to the instructions with this unit are in accordance with the requirements 

of CSA Standard C22.2, No. 141 – Unit Equipment for Emergency Lighting. 

2. Clean face(s) on a regular basis.
 

NOTE: The servicing of any parts should be performed by qualified service personnel only. The use of replacement

 

 