MAINTENANCE
1. The lamps listed herein when used according to the instructions with this unit are in accordance with the requirements of CSA Standard
C22.2, No. 141 – Unit Equipment for Emergency Lighting.
2. Clean face(s) on a regular basis.
NOTE: The servicing of any parts should be performed by qualified service personnel only. The use of replacement
parts not furnished by BeLuce Canada Inc., may cause equipment failure and will void the warranty.
SAVE THESE INSTRUCTIONS
Figure 5
Figure 1
Figure 3
Figure 2
Figure 4
Universal
Spiderplate
Electrical
Junction Box
(supplied by
others)
Frame
Faceplate
Faceplate
Cover Screw
Remove chevrons/
arrows as required
Unscrew faceplate
cover screw & slide
out faceplate
Install canopy kit as
shown if required
End Wall
mount
Ceiling
mount
Test Switch &
AC ON LED
Exit Canopy
Chassis GND
LED Board
AC ONLY SIGN
Chassis GND
GREEN Ground
BLACK 120VAC
RED 347VAC or ORANGE 200-277VAC
WHITE Neutral
LED Board
AC & UNIVERSAL DC SIGN
YELLOW Positive 6 to 24VDC
PURPLE Negative
Emergency Supply
FROM Battery Pack
SELF-POWERED SIGN
Chassis GND
24 hours
Unswitched Supply
GREEN Ground
BLACK 105 to 360VAC
WHITE Neutral
LED Board
DUAL UNIVERSAL AC SIGN
From Generator OR
Emergency Supply
BROWN 105 to 360VAC
BLUE Neutral
NOTE: Cap unused AC Wire!
NOTE: Cap unused AC Wire!
24 hours
Unswitched Supply
GREEN Ground
BLACK 120VAC
RED 347VAC or ORANGE 200-277VAC
WHITE Neutral
24 hours
Unswitched Supply
Chassis GND
LED Board
NOTE: Cap unused AC Wire!
GREEN Ground
BLACK 120VAC
RED 347VAC or ORANGE 200-277VAC
WHITE Neutral
24 hours
Unswitched Supply
Ni-Cd
Battery
926000134
BeLuce Canada Inc., 3900 14th Avenue, Markham, ON L3R 4R3 P: (905) 948-9500 F: (905) 948-8673
NOTE: STELLA EXIT FACEPLATE SHOWN BUT
INSTRUCTIONS REMAIN THE SAME.