background image

MAINTENANCE 

1.  The lamps listed herein when used according to the instructions with this unit are in accordance with the requirements of CSA Standard 

C22.2, No. 141 – Unit Equipment for Emergency Lighting. 

2.  Clean face(s) on a regular basis.

 

NOTE: The servicing of any parts should be performed by qualified service personnel only. The use of replacement

 

 

     parts not furnished by BeLuce Canada Inc., may cause equipment failure and will void the warranty.

SAVE THESE INSTRUCTIONS

Figure 5

Figure 1

Figure 3

Figure 2

Figure 4

Universal 

Spiderplate

Electrical 

Junction Box 

(supplied by 

others)

Frame

Faceplate

Faceplate

Cover Screw

Remove chevrons/

arrows as required

Unscrew faceplate 

cover screw & slide 

out faceplate

Install canopy kit as 

shown if required

End Wall 

mount

Ceiling 

mount

Test Switch & 

AC ON LED

Exit Canopy

Chassis GND

LED Board

AC ONLY SIGN

Chassis GND

GREEN Ground

BLACK 120VAC

RED 347VAC or ORANGE 200-277VAC

WHITE Neutral

LED Board

AC & UNIVERSAL DC SIGN

YELLOW Positive 6 to 24VDC

PURPLE Negative

Emergency Supply

FROM Battery Pack

SELF-POWERED SIGN

Chassis GND

24 hours

Unswitched Supply

GREEN Ground

BLACK 105 to 360VAC

WHITE Neutral

LED Board

DUAL UNIVERSAL AC SIGN

From Generator OR

Emergency Supply

BROWN 105 to 360VAC

BLUE Neutral

NOTE: Cap unused AC Wire!

NOTE: Cap unused AC Wire!

24 hours

Unswitched Supply

GREEN Ground

BLACK 120VAC

RED 347VAC or ORANGE 200-277VAC

WHITE Neutral

24 hours

Unswitched Supply

Chassis GND

LED Board

NOTE: Cap unused AC Wire!

GREEN Ground

BLACK 120VAC

RED 347VAC or ORANGE 200-277VAC

WHITE Neutral

24 hours

Unswitched Supply

Ni-Cd

Battery

926000134

BeLuce Canada Inc., 3900 14th Avenue, Markham, ON L3R 4R3 P: (905) 948-9500 F: (905) 948-8673

NOTE: STELLA EXIT FACEPLATE SHOWN BUT 

INSTRUCTIONS REMAIN THE SAME.

Reviews: