MEZZO 

AUTOTEST

Page 2 of 2

Beghelli U.S.A., 3810 Executive Way, Miramar, Florida, Tel: (954) 442-6600

07/01/22

INSTRUCTIONS

INSTRUCTIONS FOR AUTOTEST:

Once the unit is properly installed according to the installation instruction sheet and AC power supplied, the dual color LED indicator will come 
ON and the Autotest function will automatically initiate. The LED indicates the unit’s status. A STEADY GREEN LED indicates normal service; 
FLASHING GREEN indicates the unit is testing; GREEN/RED FLASHING indicates the battery is charging; RED (in different combinations) would 
indicate a service alert. Refer to the Service Indication chart below for more details. The LED would be OFF with the unit is in emergency mode.

AUTOTEST SERVICE

The Autotest function is factory preset and performs the following:
a.  Monitoring of battery, battery charger and lamps.
b.  Self-testing and a 30-second or longer discharge once every 30 days, after the AC power has been supplied for a minimun of 24 hours.
c.  Self-testing and a 30-second or longer discharge once every 180 days, after the AC power has been supplied for a minimun of 24 hours.
d.  Self-testing and a 90-second discharge once every 365 days, after the AC power has been supplied for a minimun of 24 hours.

LED Indicator

Status

One Flash Red

Replace Electronics

Two Flash Red

Replace Battery

Four Flash Red

Replace Lamp Head Board

Steady Red

Battery Disconnected

Sold Green

Trickle Charge

Flashing Green

In Test

Red/Green Flashing High Charge

SERVICE INDICATION

Action

Reaction & LED Indication

Press test button once

(within 2 seconds) 30-second test: FLASHING GREEN

Press test button twice

(within 2 seconds) 30-minute test: GREEN FLASHING TWICE

Press test button 3 times (within 2 seconds) 90-minute test: GREEN FLASHING THREE TIMES

Press test button and 

hold for 3 seconds.

(in test mode)

Cancels test. If Autotest is cancelled, it is recommended that a manual test of the same 

duration be performed at a more convenient time to ensure compliance.

Press test button and 

hold for 6 seconds.

(in test mode)

System reset.

MANUAL TESTING

The unit also provides for manual testing by pushing the test button in a specific pattern.

WARNING:

a)  Make sure that power is OFF before making any electrical connections.
b)  Unused wires must be capped using enclosed wire nuts.