Testing – 6
6–39
79 Reconnect
VOLTAGE INPUTS:
Configuration V1
CURRENT INPUTS:
None
TEST SETTINGS:
Time Delay
D
Cycles
(2 to 65,500)
Reconnect Initiate
R
(1 to 8)
Programmed Outputs
Z
Output
(1 to 8)
1.
Confirm settings to be tested.
2.
Connect inputs in Configuration V1 as designated previously. Refer to Section 6.4,
Input Configurations
for configuration.
3.
Adjust the three-phase source to Nominal Voltage.
4.
Setup
: Remove the A phase voltage input to cause Function 27 to trip Output
R
(Output
R
will trip
after Function 27 times out).
5.
Time Test
: With output contacts connected to the timer, reapply the A phase voltage input and start
timing. The operation time will be D cycles within
&
2 cycles.
6.
Press
TARGET/OUTPUT RESET
pushbutton to remove targets.
7.
If testing is complete, enable any functions disabled for this test. If further testing is desired, check
the proper functions to disable for the next test and continue from this point.