Technical data, mounting, wiring
PS2001-2410-0000
23
Version: 1.0
3.14
Environment
Environment
Operating temperature
1)
-25°C to +70°C
Reduction of the output power according to
Fig.
Output current over ambient temperature
Storage temperature
-40°C to +85°C
For storage and transport
Output load reduction
3.2W/°C 6W/°C
+45°C to +60°C / +60°C to +70°C
Moisture
5 to 95% r.h.
According to IEC 60068-2-30 Do not
energize if there is condensation.
Oscillation, sinusoidal
2)
2–17.8Hz: ±1.6mm;
17.8-500Hz: 2g 2 hours/axis
According to IEC 60068-2-6
Impacts
2)
30g 6ms, 20g 11ms 3 impacts /
direction, 18 impacts in total
According to IEC 60068-2-27
Installation altitude
0 to 2000m
Without any restrictions
2000 to 6000m
Reduce the output power or ambient
temperature, see Fig.
Output current over
installation altitude
.
Load reduction due to
installation altitude
15W/1000m or 5°C/1000m
Above 2000m, see Fig.
Output current over
installation altitude
Overvoltage category
III
According to IEC 62477 -1, installation
altitudes up to 2000m
II
According to IEC 62477-1, installation
altitudes between 2000m and 6000m
Degree of pollution
2
According to IEC 62477-1, non-conductive
LABS-free
The device does not release any silicones or other paint-wetting impairment
substances and is suitable for use in paint shops.
Corrosive gas
ISA-71.04-1985, Severity Level G3, IEC 60068-2-60 Test Ke Method 4
Audible noises
In the event of no-load, overload or short circuit, the power supply unit emits
audible noises.
1)
The working temperature is identical to the room temperature or the ambient temperature and is defined as
the air temperature 2cm below the device.
2)
Tested in conjunction with DIN rails according to EN 60715 with a height of 15mm and a thickness of
1.3mm and standard mounting position.
Fig. 15: Output current over ambient temperature; output current over installation altitude