Technical data, mounting, wiring
PS2031-2410-0000
11
Version: 1.0
3
Technical data, mounting, wiring
3.1
AC input
The device is suitable for being supplied with AC voltage from TN, TT and IT networks. Earthing of one
phase is permitted, except for UL508 applications.
The device can also be operated at only two phases of a three-phase system. For further information see
chapter
AC input
AC input
Nom.
3AC 380-480V
Suitable for TN, TT and IT networks
AC input range
Min.
3x 323-576Vac
Continuous operation
Min.
3x 576-700Vac
For up to 1000ms max.
Permissible voltage L or N to earth
Max.
500 Vac
Continuous according to IEC 62477-1
Input frequency
Nom.
50–60Hz
±6%
Turn-on voltage
Typ.
3x 260Vac
Static, see Fig.
Input voltage range; switch-on behavior
definitions
Shut-down voltage
Typ.
3x 185Vac
Static, see Fig.
Input voltage range; switch-on behavior
definitions
AC input
3AC 400V
3AC 480V
Input current
Typ.
0.7A
0.6A
At 24 V, 10 A per phase, see Fig.
Input current over
output current; power factor over output current
Power factor*)
Typ.
0.53
0.52
At 24 V, 10 A, see Fig.
Input current over output cur-
rent; power factor over output current
Start-up delay
Typ.
90 ms
90 ms
See Fig.
Input voltage range; switch-on behavior defini-
tions
Rise time
Typ.
40 ms
40 ms
At 24 V, 10 A constant current load, 0 mF load capac-
ity, see
Fig. Input voltage range; switch-on behavior
definitions
Typ.
85 ms
85 ms
At 24 V, 10 A constant current load, 10 mF load capac-
ity, see Fig.
Input voltage range; switch-on behavior
definitions
Turn-on overshoot
Max.
200 mV
200 mV
See Fig.
Input voltage range; switch-on behavior defini-
tions
*) The power factor is the ratio of real (or active) power to apparent power in an AC circuit.
Fig. 1: Input voltage range; switch-on behavior definitions