Mounting and wiring
KM2604 and KM2614
14
Version: 2.1.0
3
Mounting and wiring
3.1
Recommended mounting rails
Terminal Modules and EtherCAT Modules of KMxxxx and EMxxxx series, same as the terminals of the
EL66xx and EL67xx series can be snapped onto the following recommended mounting rails:
• DIN Rail TH 35-7.5 with 1 mm material thickness (according to EN 60715)
• DIN Rail TH 35-15 with 1,5 mm material thickness
Note
Pay attention to the material thickness of the DIN Rail
Terminal Modules und EtherCAT Modules of KMxxxx and EMxxxx series, same as the ter-
minals of the EL66xx and EL67xx series does not fit to the DIN Rail TH 35-15 with 2,2 to
2,5 mm material thickness (according to EN 60715)!
3.2
Dimensions
Fig. 10: Dimensions
Width of a bus terminal block
Attention
Note the maximum number of Bus Terminals
The maximum number of Bus Terminals or terminal modules that can be connected to a
Bus Coupler is 64!
An overall width of 80 cm must not be exceeded!
Also ensure that the current consumption of the Bus Terminals/terminal modules from the