Product Overview
KL8001 and KL9060
12
Version: 2.0.0
2.3
Power terminal KL8001 - Technical data
KL8001
Power Terminal
Number of power terminals per Bus Coupler 10 max.
If you operate two contactors with each power terminal (reversing
contactor connection) then you may only use 5 power terminals with
each Bus Coupler.
Observe also the
that your Bus Coupler can
supply to the K-bus!
Number of contactors per Bus Coupler
10 max.
Type of fastening and mechanical connec-
tion
Suitable for Siemens contactors of the Sirius 3RT10 series, size S00
Type of connection power path
Screw terminals for core cross-sections up to 2 x 2.5 mm
2
Power path current loading (back-up fuse)
25 A max.
Power path short-circuit strength
up to 5000 A
Power path internal resistance
< 1 mΩ
Setting range of rated current
: 0.9 A to 9.9 A
Selectable tripping classes
CLASS 5, 10, 15, 20, 25, 30 selectable
Measured values
Current, voltage, effective power, cos
j
, energy consumption, switching cycles, operating
hours
Measuring accuracy (at balanced load)
0.15 A
rms
; 2 V
rms
; 5 W; 1 kWh
Crosstalk between the channels at unbal-
anced load
up to 3% from the difference
Measuring voltage
500 V
Type of K-bus connection
2 x flat plug socket, 10 pin
K-bus current consumption (5 V
DC
)
typically 150 mA
Observe the
that your Bus Coupler can supply to the K-bus!
Contactor control voltage current consump-
tion (24 V
DC
)
When contactor switched off: typically 7 mA
When contactor switched on: typically 7 mA + current in the contactor coil
Dielectric strength
500 V
(power contact/K-bus), 6000 V
(mains supply/K-bus)
Behavior under short-circuit conditions
conforms to EN 60947-4-1 (assignment type 2)/VDE 102
Triggering tolerance
conforms to IEC 947, as well as UL and CSA
Configuration options
Automatic over the fieldbus using the KS2000 configuration software, manual (rated cur-
rent)
Width in the process image
96 bits I/O (see description of the
)
Permissible ambient temperature range dur-
ing operation
0°C ... +55°C
Permissible ambient temperature range dur-
ing storage
-25°C ... +85°C
Permissible relative air humidity
95 %, no condensation
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Weight
approx. 90 g
Dimensions (W x H x D)
approx. 45 mm x 69 mm x 74 mm
Mounting
With lugs and connecting pins to Siemens contactors of the 3RT1016 series
Installation position
variable (although you must observe the permitted installation positions of the contactors)
Protection class
IP20
Approvals
CE
Summary of Contents for KL8001