Product Overview
KL8001 and KL9060
10
Version: 2.0.0
2.2
KL8001 Power terminal - Functional description
Rotary switches for adjusting the rated current
You can set the motor's rated current manually using the two rotary switches on the power terminal. The
upper rotary switch operates in 1 A steps, while the lower switch provides 0.1 A steps. You can thus set
values between 0.9 A and 9.9 A. The value set then applies to all three phases.
If you set the two rotary switches to zero, you must specify the rated motor current using the three parameter
registers
. You can then:
• set the rated current separately for each phase, if three different single-phase motors are connected,
for example.
• use the extended setting range of 10.0 A to 15.0 A, which cannot be set via the rotary switches.
Fig. 2: KL8001 - rotary switch for setting the rated current
LEDs
Fig. 3: KL8001 - LEDs
The power terminal has 4 LEDs for status display to enable rapid diagnosis. The possible states are listed in
the following table.
LED
State
Description
on (motor)
on
Motor is running, either to the right or left
off
Motor is switched off, or overload protection has triggered
overload (motor)
on
Motor has been switched off due to overload
flashes (2 Hz)
Power has fallen below minimum load threshold
flashes (5 Hz)
Overload threshold has been exceeded
off
Nominal operation (load neither below minimum and or above maximum), or motor is
switched off
run (fieldbus)
on
Communication with the terminal bus is taking place without errors
off
No communication with the terminal bus (watchdog timer has triggered after 100 ms)
stop (fieldbus)
on
No communication with the terminal bus
flashes
Error code and error argument are indicated as flashing code
off
Communication with the terminal bus is taking place without errors