Access from the user program
KL8001 and KL9060
42
Version: 2.0.0
Examples
Read the active power of phase L1:
• Enter data register number 5 into
.
• The content of register DR5 in register set 1 is returned in process data word
Read the energy consumption of phase L2:
• Enter data register number 8 into
.
• The content of register DR8 in register set 2 is returned in process data word
Read cos phi for phase L3:
• Enter data register number 6 into
.
• The content of register DR6 in register set 3 is returned in process data word
5.3.1
Status word
The status word contains further information about the state of the KL8001. Under
it can be transmitted from the terminal to the controller using any of the
or
Status word
Bit
SW.15 SW.14 SW.13 SW.12 SW.11 SW.10 SW.9
SW.8
SW.7
SW.6
SW.5
SW.4
SW.3
SW.2
SW.1
SW.0
Key
Bit
Name
Value Description
SW.15
Other errors
1
bin
another error has occurred
SW.14
No rated current set
1
bin
Both the two rotary switches and
• register
not active) or
• at least one of registers
or
(single-phase analysis is active)
SW.13
Contactor fault
1
bin
Current flow detected with contactor switched off
SW.12
reserved
-
-
SW.11
reserved
-
-
SW.10
reserved
-
-
SW.9
Overvoltage L3
1
bin
Voltage > configured overvoltage limit (
)
SW.8
Overvoltage L2
1
bin
Voltage > configured overvoltage limit (
)
SW.7
Overvoltage L1
1
bin
Voltage > configured overvoltage limit (
)
SW.6
Undervoltage L3
1
bin
Voltage < configured undervoltage limit (
)
SW.5
Undervoltage L2
1
bin
Voltage < configured undervoltage limit (
)
SW.4
Undervoltage L1
1
bin
Voltage < configured undervoltage limit (
)
SW.3
Phase failure in L3
1
bin
Failure of phase L3
SW.2
Phase failure L2
1
bin
Outage of phase L2
SW.1
Phase failure L1
1
bin
Outage of phase L1
SW.0
Asymmetric load
1
bin
Current difference > configured current difference (
)