Product Overview
KL8001 and KL9060
14
Version: 2.0.0
2.5
Adapter terminal KL9060 - Technical data
KL9060
Adapter terminal
Power contacts voltage (ribbon cable)
24 V
DC
(-15%, +20%)
Power contacts current loading (ribbon
cable)
maximum 1400 mA (short-circuit proof).
Observe the current consumption of the power terminals and the
contactor coils!
Voltage of the K-bus power supply (ribbon
cable)
5 V
DC
Current consumption of the K-bus power
supply (ribbon cable)
maximum 2000 mA
Observe the maximum current that your Bus Coupler can supply
to the K-bus! Examples:
• Low Cost Coupler: 500 mA
• Economy Coupler: 500 mA
• Economy Plus Coupler: 1750 mA
• Standard Coupler: 1750 mA
• KL9400 Power Supply Terminal: 2000 mA
Use the KL9400 Power Supply Terminal if the current
consumption of your terminals exceeds the maximum current
that your Bus Coupler can feed to the K-bus supply.
Number of power terminals per KL9060
10 max.
If you operate two contactors with each power
terminal (reversing contactor connection) then you
may only use 5 power terminals with each KL9060.
Observe also the
Bus Coupler can supply to the K-bus!
Number of contactors per KL9060
10 max.
Permissible ambient temperature range
during operation
0°C ... +55°C
Permissible ambient temperature range
during storage
-25°C ... +85°C
Permissible relative air humidity
95 %, no condensation
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Weight
approx. 50 g
Dimensions (W x H x D)
approx. 33 mm x 100 mm x 70 mm
Mounting
on 35 mm mounting rail conforms to EN 60715
Installation position
variable
Protection class
IP20
Approvals
CE