Access from the user program
KL6781
22
Version: 2.0.0
4.4
Mapping
The Bus Terminals occupy addresses within the process image of the controller. The assignment of process
data (input and output data) and parameterization data (control and status bytes) to the control addresses is
called mapping. The type of mapping depends on:
• the fieldbus system used
• the terminal type
• the parameterization of the Bus Coupler (conditions) such as
◦ compact or complex evaluation
◦ Intel or Motorola format
◦ word alignment switched on or off
The following tables show the mapping depending on different conditions. For the content of the individual
bytes please refer to pages
and
.
Compact evaluation
Note
No compact process image
The KL6781 cannot be operated with a compact process image (without control and status
word), since the control and status words are required for meaningful process data mode
operation of the terminal. The KL6781 is represented with its complex process image, even
if you set your Bus Coupler to a compact process image!
Complete evaluation
Complete evaluation in Intel format
Address
Input data
Output data
Conditions
Word offset
High byte
Low byte
High byte
Low byte
Complete evaluation: any
Motorola format: no
Word alignment: any
0
SW
CW
1
DataIN 1
DataIN 0
DataOUT 1
DataOUT 0
2
DataIN 3
DataIN 2
DataOUT 3
DataOUT 2
3
DataIN 5
DataIN 4
DataOUT 5
DataOUT 4
4
DataIN 7
DataIN 6
DataOUT 7
DataOUT 6
5
DataIN 9
DataIN 8
DataOUT 9
DataOUT 8
6
DataIN 11
DataIN 10
DataOUT 11
DataOUT 10
7
DataIN 13
DataIN 12
DataOUT 13
DataOUT 12
8
DataIN 15
DataIN 14
DataOUT 15
DataOUT 14
9
DataIN 17
DataIN 16
DataOUT 17
DataOUT 16
10
DataIN 19
DataIN 18
DataOUT 19
DataOUT 18
11
DataIN 21
DataIN 20
DataOUT 21
DataOUT 20