Technical data
Technical data
KL3208-0010
KL3228-0000, KS3228-0000
Inputs
8
Sensor types
PT1000 (default), Ni1000,
Potentiometer: 1kΩ /5kΩ / 10kΩ,
NTC: 1.8k / 2.2k / 3k / 5k / 10k /
20k / 100k
PT1000 (default), Ni1000
Wiring
2-wire
1-wire
Terminal points
High Density (HD)
standard (KL)
pluggable (KS)
Temperature range Pt sensors
-50°C…+150°C
Ni sensors
-50°C…+150°C
Conversion time
approx. 1 s
Measuring current
typically 0.5 mA
Resolution
0.01°C per digit
0.1°C per digit
Measuring error (full measuring
range)
-20°C…+60°C: ±0.25 °C
(at 25 °C ambient temperature)
-50°C…+150°C: ±1.5 °C
±1.0 °C, depending on wiring
Bit width in the input process image 8 status bytes (optional), 8 data words
Bit width in the output process
image
8 control bytes (optional), 8 data words (optional)
Power supply for the electronics
via the K-bus
Current consumption from K-bus
typically 85 mA
Electrical isolation
500 V (K-Bus/signal voltage)
Weight
approx. 75 g
approx. 75 g
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm
on 35 mm mounting rail conforming to EN 60715
Pluggable wiring
-
at all KSxxxx series terminals
Permissible ambient temperature
range during operation
-25 °C ... +60 °C (extended
temperature range)
0°C ... + 55°C
Permissible ambient temperature
range during storage
-40 °C ... + 85 °C
-25 °C ... + 85 °C
Permissible relative air humidity
95 %, no condensation
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
see also
Installation instructions for enhanced mechanical load
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
CE,
ATEX (extended temperature
range) [
,
cULus
CE,
ATEX (standard temperature
range) [
,
cULus