Access from the user program
KL2532/KS2532, KL2552/KS2552
55
Version: 3.2.0
Command 0x7000: Restore Factory Settings
KL2532
An entry of 0X7000 in register R7 sets the following registers for the two channels to the following default
values:
R32: 0
dec
dec
2500
dec
1500
dec
24000
dec
:
1500
dec
: 0
dec
:
100
dcz
:
2000
dec
:
200
dec
: 100
dec
: 1500
dec
: 400
dec
: 4
dec
: 0
dec
: 0
dec
KL2552
An entry of 0X7000 in register R7 sets the following registers for the two channels to the following default
values:
R32: 0
dec
dec
5000
dec
1000
dec
50000
dec
100
dec
dec
dec
: 0
dec
:
2500
dec
: 0
dec
: 0
dec
: 0
dec
:
100
dec
:
2000
dec
:
200
dec
: 100
dec
: 2500
dec
: 400
dec
: 4
dec
: 0
dec
: 0
dec
: 0
dec
: 0
dec
Restore Factory Settings resets both channels
The command Restore Factory Settings simultaneously resets both channels of the DC motor out-
put stage terminal to the delivery state, irrespective of which register set it is called!
WARNING
Risk of injury!
This command is used to de-energies the motor. Ensure that your system state permits this and that haz-
ards for persons or machinery have been ruled out!
Command 0x8000: Software Reset
Entering 0x8000 in register R7 initiates a full software reset for the terminal. All internal variables (positions,
latched values, errors, etc.) are cleared or are set to defined values that are read from the EEPROM. The
internal circuits (ADC, output driver) are reinitialized with a software reset.
WARNING
Risk of injury!
During a software reset the motor is switched current-free. Ensure that your system state permits this and
that hazards for persons or machinery have been ruled out!
R8: Terminal type
The terminal identifier is contained in register R8: 0x09F8 (2552
dec
)