Product overview
KL1501, KL1512
10
Version: 3.1.0
2.3
KL1501, KL1512 - Technical data
Technical data
KL1501
KL1512
Connection technology
1 x up/down counter, 2 x up or down counter
Specification
EN 61131-2, type 1, “0”: < 5 V
DC
, “1”: > 15 V
DC
, typ. 5 mA
Number of counters
1 or 2
Rated load voltage
24 V
DC
(-15 %/+20 %)
Signal voltage ‘0’
-3 V…+5 V (EN 61131-2, type 1)
Signal voltage ‘1’
15 V…30 V (EN 61131-2, type 1)
Input current
typically 5 mA (EN 61131-2, type 1)
Switching frequency
max. 100 kHz (2 kHz for up/down
switching)
max. 1 kHz
Counter depth
32 bit or 2 x 16 bit
16 Bit
Max. output current
24 V / 0.5 A typ. (short-circuit-proof)
per channel
-
K-bus current consumption
typically 50 mA
Current consumption power
contacts
only load
Electrical isolation
500 V (K-bus / field voltage)
Bit width in the process image
40 I/O: 32 bit data, 8 bit control/
status
2 x 16 Bit data 2 x 8 Bit control/
status
Configuration
no address setting, configuration
via the Bus Coupler or the
controller
no address setting, configuration
via the control byte and status byte.
Special features
2 additional outputs
Set counters
Weight approx.
50 g
Permissible ambient temperature
at operation
-25 °C ... +60 °C (extended temperature range)
Permissible ambient temperature
at storage
-40 °C ... +85 °C
Permissible relative humidity
95%, no condensation
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27,
see also
Installation instructions for enhanced mechanical load capacity
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Installation position
any
Protection class
IP20
Approvals
CE,
cULus,
IECEx,
CE,
cULus,