Commissioning/Configuration
EP3356-0022
45
Version: 1.4
Permanent tare
• The correction value is stored locally in the boxes EEPROM and is not lost in the event of a power
failure. To this end the command "0x0002" is executed on CoE object
(binary dialog
in the System Manager: "02 00"). This sets the tare object (
value is 0.
Local storage
The values modified during the theoretical and practical calibration are stored in a local EEPROM.
This can be written to up to 1 million time. In order to prolong the life of the EEPROM, therefore, the
commands should not be executed cyclically.
Commands
The functions discussed above are carried out by means of commands in the standardized object
.
Index
Name
Comment
FB00:01
Request
Entry of the command to be executed
FB00:02
Status
Status of the command currently being executed
0: Command executed without error
255: Command is being executed
FB00:03
Response
Optional response value of the command
The function blocks
FB_EcCoESdoWrite
and
FB_EcCoESdoRead
from the
TcEtherCAT.lib
(contained in the
standard TwinCAT installation) can be used in order to execute the commands from the PLC.
Commands of the EP3356
The following commands can be transferred to the box via the CoE entry
.
Command
Comment
0x0101
Execute zero balance
0x0102
Execute calibration
0x0001
Execute tare procedure (value is NOT saved in the boxes EEprom)
0x0002
Execute tare procedure (value is saved in the boxes EEprom)