Parameterization and programming
ELX3351
60
Version: 1.3.1
5.6.2
Configuration data
Index 8000 RMB Settings
Index (hex) Name
Meaning
Data type
Flags
Default
8000:0
RMB Settings
Max. subindex
UINT8
RO
0x32 (50
dec
)
8000:01
Enable filter
0: No filters active. The terminal operates cycle-syn-
chronous
1: The filter settings selected in subindex 0x8000:11
or 0x8000:12 are active.
BOOLEAN
RW
0x01 (1
dec
)
8000:03
Enable averager
Activate hardware mean value filter
BOOLEAN
RW
0x01 (1
dec
)
8000:05
Symmetric reference
potential
Activate symmetric measurement
BOOLEAN
RW
0x01 (1
dec
)
8000:11
Mode0 filter settings
0: FIR 50 Hz
1: FIR 60 Hz
2: IIR 1
3: IIR 2
4: IIR 3
5: IIR 4
6: IIR 5
7: IIR 6
8: IIR 7
9: IIR 8
10: Dynamic IIR
UINT16
RW
0x0000 (0
dec
)
8000:13
Dynamic filter change
time
Sampling rate for dynamic filter switching.
Scaling in 0.01 ms (100 = 1 s)
(only if the filters are active and "dynamic IIR" is se-
lected as filter)
UINT16
RW
0x000A (10
dec
)
8000:14
Dynamic filter delta
Limit value for dynamic filter switching.
(only if the filters are active and "dynamic IIR" is se-
lected as filter)
REAL32
RW
0x41A00000
(1101004800
dec
) =
20.0
8000:21
Gain
Scale factor
REAL32
RW
0x3F800000
(1065353216
dec
) =
1.0
8000:22
Tare
Process data value offset
REAL32
RW
0x00000000 (0
dec
) =
0.0
8000:23
Rated output
Nominal characteristic value of the sensor element in
mV/V
REAL32
RW
0x40000000
(1073741824
dec
) =
2.0
8000:24
Nominal load
Nominal load of the force transducer/load cell/etc.
(e.g. in kg, N or ...)
REAL32
RW
0x40A00000
(1084227584
dec
) =
5.0
8000:25
Zero balance
Zero point offset in mV/V
REAL32
RW
0x00000000 (0
dec
) =
0.0
8000:26
Gravity of earth
Current acceleration of gravity (default 9.806650)
REAL32
RW
0x411CE80A
(1092413450
dec
) =
9.806650
8000:27
Scale factor
This factor can be used to re-scale the process data.
In order to change the display from kg to g, for exam-
ple, the factor 1000 can be entered here.
REAL32
RW
0x447A0000
(1148846080
dec
) =
1000.0
8000:28
Reference load
Reference weight for manual calibration
REAL32
RW
0x40A00000
(1084227584
dec
) =
5.0
8000:29
Steady state window
Time constant for the "steady state" bit (used for idle
recognition)
UINT16
RW
0x03E8 (1000
dec
)
8000:2A
Steady state toler-
ance
Tolerance window for the "steady state" bit
UINT32
RW
0x00000005 (5
dec
)
8000:31
Calibration interval
Calibration interval for automatic calibration of the
terminal.
The unit is 100 ms.
The smallest possible value is 5 (500 ms). A value of
0 deactivates automatic self-calibration. This is also
possible via the process data bit "Disable calibration".
UINT16
RW
0x0708 (1800
dec
)