Product overview
EL28xx-xxxx
42
Version: 2.2
2.5.6.4
Input data
Index 60n1 DIG Diag Inputs
(n=0 for Ch.1…n=9 for Ch.10; n=A for Ch.11…n=F for Ch.16)
Index (hex) Name
Meaning
Data type
Flags
Default value
60n1:0
DIG Diag Inputs Ch.n
Maximum subindex
UINT8
RO
0x04 (4
dec
)
60n1:01
The overtemperature bit is set if the max. permissible
temperature of the channel is exceeded.
BOOLEAN
RO
0x00 (0
dec
)
60n1:02
Wire break detection
The Open Load bit is set if the channel is switched on
and the load current is ≤ typically 0.2 mA.
BOOLEAN
RO
0x00 (0
dec
)
60n1:03
Overcurrent and short-circuit detection
The overcurrent bit is set if an overload is detected
when the channel is switched on.
No overload can be detected if the channel is switched
off (e.g. thermal switch-off).
Short-circuit current detection: typ. 1 A
BOOLEAN
RO
0x00 (0
dec
)
60n1:04
The Short Circuit to 24V bit is set if voltage is present
when the channel is switched off.
BOOLEAN
RO
0x00 (0
dec
)
Index F600 DIG Inputs Device
Index (hex) Name
Meaning
Data type
Flags
Default value
F600:0
DIG Inputs Device
Maximum subindex
UINT8
RO
0x14 (20
dec
)
F600:11
The Common Fault bit is set if an error occurs on one
or more channels of the terminal.
BOOLEAN
RO
0x00 (0
dec
)
F600:12
The Overtemperature Device bit is set if the max. per-
missible device temperature is exceeded.
The overloaded channels are switched off until the de-
vice temperature cools down below the lower limit
value again.
BOOLEAN
RO
0x00 (0
dec
)
F600:13
The Undervoltage bit is set if the terminal supply volt-
age falls below typically 17 V.
BOOLEAN
RO
0x00 (0
dec
)
F600:14
The Missing Voltage bit is set if the supply voltage is
lower than typically 14 V.
BOOLEAN
RO
0x00 (0
dec
)
2.5.6.5
Output data
Index 70n0 DIG Outputs
(n=0 for Ch.1…n=9 for Ch.10; n=A for Ch.11…n=F for Ch.16)
Index (hex) Name
Meaning
Data type
Flags
Default value
70n0:0
DIG Outputs Ch.n
Maximum subindex
UINT8
RO
0x01 (1
dec
)
70n0:01
Output
Status Output
0: Output off
1: Output on
BOOLEAN
RO
0x00 (0
dec
)
2.5.6.6
Standard objects
Standard objects (1000-1FFF)
Index 1000 Device type
Index (hex) Name
Meaning
Data type
Flags
Default value
1000:0
Device type
Device type of the EtherCAT slave: the Lo-Word con-
tains the CoE profile used (5001). The Hi-Word con-
tains the module profile according to the modular de-
vice profile.
UINT32
RO
0x01181389
(18355081
dec
)