Product overview
CX8030 / CX8031
17
Version: 1.6
4.4
Technical data - PROFIBUS
System data
PROFIBUS (CX8030, CX8031)
Number of I/O
modules
100 with repeater
Number of I/O
points
approx. 6.000, depending on the master
Transmission
medium
screened copper cable, 2 x 0.25 mm²
Cable length
1200 m
1000 m
400 m
200 m
100 m
Data transfer rate
9,6/19,2/93,75
kBaud
187,5 kBaud
500 kBaud
1500 kBaud
3, 6, 12 MBaud
Topology
Line topology
CX8030
Technical data - PROFIBUS
CX8030
Fieldbus
PROFIBUS DP, DP-V1
Data transfer rate
9,6k; 19,2k; 93,75k; 187,5k; 500k; 1,5M; 3M; 6M; 12
MBaud
Bus interface
1 x D-sub socket, 9-pin
Bus devices
max. 125 with repeater
max. process image
30,5 kByte in / 30,5 kByte out
Protokoll
PROFIBUS-DP
Yes
PROFIBUS-FMS
No
ADS Interface
Yes (only via Ethernet)
Services
PROFIBUS
DP
DPV1 class 1
Yes
DPV1 class 2
No
DPV2 MC
No
Redundancy
No
Muti Master
No
FDL
No
S5 AG-AG
No
Activating slaves via ADS
Yes
PKW
No
Diagnosis/Status/Alarm
TC LED
Yes, green/red
BF LED
Yes, green/red
DIA LED
Yes, green/red (no function)