Commissioning
CX2900-0192
22
Version: 1.4
5.2.3
Connect battery pack
Together with the CX2100-0914 power supply unit, the CX2900-0192 battery pack is capable of supplying
power to the Embedded PC in case of power failures. The power supply unit and the battery pack are
connected to each other by two cables. In normal operation the battery pack is charged by the power supply
unit. In the event of a power failure the battery pack supplies the Embedded PC with power via the power
supply unit.
If a further device such as a control panel or monitor is connected to the
X940 OUT
connection (+24 V, 0 V,
earth), this device will also be supplied with power by the battery pack in the event of a power failure (see:
).
The plugs for the cabling are supplied with the power supply unit and can be re-ordered.
Requirements:
• Cable for the power supply (+24 V, 0 V, earth) with a conductor cross-section of 1.5 mm².
• RJ45 Ethernet cable, Cat-5 standard with four wire pairs. Crossover cables are not supported.
• The cables must not be any longer than 5 m.
Connect the battery pack as follows:
1. Switch off the supply of power to the power supply unit.
2. Configure the cable (+24 V, 0 V, earth) and mount the cable on the plugs supplied.
3. Make sure that the cables on the connections on the
X940 BAT
power supply unit and on the
X101 BAT
battery pack are correctly configured (+24 V, 0 V, earth).
0V
+24V
- BAT
FAIL
+ BAT
0V
OUT
BAT
SIG
BAT control
Shielding
Grounding busbar
4. Connect one end of the RJ45 Ethernet cable to the
X941 BATTERY
connection of the power supply unit.
5. Connect the other end of the cable to the
X102
connection of the battery pack.
6. Insert the fuse (10 A ff) into the battery pack.