Commissioning
CP29xx-2xxx-0000
23
Version: 1.3
4.3.1
Installing the supply cable
Install the cable for the power supply of the Control Panel using the material supplied for connector
assembly. It consists of a 5-pin connection strip and a strain relief housing with cable tie.
If you require a replacement for the voltage connector or the strain relief housing, you can order these from
Beckhoff Sales using the following ordering option:
• C9900-P927: Power supply connector for multi-touch built-in Control Panel CP29xx, 5-pin connector
with strain relief for the external supply cable
Installing the supply cable
First mount the plug on the cable as follows:
1. Remove the insulation from the cable ends (8-9 mm).
2. Crimp the ferrules onto the stripped cable ends.
3. Insert the cable ends with the ferrules into the 5-pin connection strip. The pin assignment of the
connector can be found in chapter 3.2.1 Power supply (for CP29xx-0000) or chapter 3.3.1 Power supply
(for CP29xx-0010).
4. Screw the cable ends into the 5-pin connection strip.
Assembly of the strain relief housing
Now mount the strain relief housing on the previously connected plug and supply cable as shown in Fig. 18:
1. Thread the cable tie into the lower part of the strain relief housing (section A).
2. Insert the connection strip into the lower part of the strain relief housing (section B).
3. Tighten the cable tie and remove the plastic tab (section C).
4. Attach the upper part of the strain relief housing by snapping it onto the lower part (section D).
A
B
C
D
Fig. 13: CP29xx_assembly of strain relief housing
To remove the strain relief housing, proceed as follows:
1. Use your fingers to bend the latching lugs on the lower part slightly outwards (see Fig. 19).
2. Lever the upper part off the lower part.
3. Cut the cable tie.