Installation Instructions
Connecting Power Supply
The external wiring consists of the connection of the power supply, the
battery pack (optional) and the connection of customised components for
shutting down the PC.
Cable Cross Sections
Note cable cross sections,
avoid voltage drop!
For the connection of the power supply, wiring with a cable-cross-section
of 1,5 mm
2
must be used.
With bigger distances between voltage source and PC, you take the
voltage drop as a function of the cable-cross-section as well as voltage
fluctuations of your distribution voltage into account, so that is secured that
the voltage doesn't fall under 22 V at the power supply.
Insert Fuse
The power supply must be protected with maximum 16 A.
PC_ON, Power-Status, UPS output
The circuit for shutting down the Industrial PC is realized using the input-
signal
PC_ON
and the output-signal
Power-Status
:
•
The PC starts shutting down if 24 V exists at
PC_ON
, for example
using a switch.
•
After shutting down, the output-voltage of 24 V at
Power-Status
is
switched to 0 V. This allows connecting an air gap switch for
disconnecting the system from power supply. The maximum
current loading of the Power-Status output is 0.5 A.
•
After power failure, there are still 24 V DC between
UPS output
and
Battery - Pole
, current loading maximum 1.4 A.
•
After the PC is disconnected from power supply via UPS software,
the UPS output is switched to 0V too. A connected Panel is thus
switched off, a total-discharge of the battery is not possible.
C63xx
17