Mechanical installation
External brake resistor AX2090-BW5x
11
Version: 1.3
4
Mechanical installation
4.1
Mounting positions and distances
(A) = vertical installation is only permitted according to the diagram (terminal box facing downwards).
(B) = horizontal installation
Assignment of the device classes
AX2090-BW50-xxxx
AX2090-BW51-1000
AX2090-BW51-3000 and AX2090-BW51-6000
AX2090-BW52-3000 and AX2090-BW52-6000
AX2090-BW53-3000 and AX2090-BW53-6000
AX2090-BW54-3000 and AX2090-BW54-6000
For all mounting positions the following minimum distances must be adhered to:
200 mm to adjacent components, walls etc. and 300 mm to components, ceilings etc. above. If the device is
installed vertically (A), the minimum distance to components, floors etc. below is 200 mm in order to allow
unobstructed flow of air to the brake resistor.