background image

6

Form 6104 BCF10-R06

Combustion air supply

The burner requires combustion air and ventilation air for 
reliable operation. Assure that the building and/or com-
bustion air openings comply with National Fire Protec-
tion Standard for Oil-Burning Equipment, NFPA 31. For 
appliance/burner units in confi ned spaces, the room must 
have an air opening near the top of the room plus one near 
the fl oor, each with a free area at least one square inch per 
1,000 Btu/hr input of all fuel burning equipment in the 
room. For other conditions, refer to NFPA 31 (CSA B1139-
M91 in Canada).

If there is a risk of the space being under negative pres-
sure or of exhaust fans or other devices depleting available 
air for combustion and ventilation, the appliance/burner 
should be installed in an isolated room provided with out-
side combustion air.

 Clearances

With the burner installed in the appliance, there must be 
adequate space in front of and on the sides of the burner 
to allow access and operation. Verify that the clearance di-
mensions comply with all local codes and with the appli-
ance manufacturer’s recommendations.

Fuel supply

The fuel supply piping and tank must provide #1 or #2 fuel 
oil at pressure or vacuum conditions suitable for the fuel 
unit (oil pump) on the burner. Refer to fuel unit literature in 
the literature envelope in the burner carton to verify allow-
able suction pressure.

‰
y

y

‰
y

‰

y

If fuel supply is 

level with or higher than

 fuel unit

 —

When the fuel unit is not required to lift the oil, the instal-
lation is usually suitable for either a one-pipe or two-pipe 
oil system. The oil pressure at the inlet of the fuel unit must 
not exceed 3 psig.
See 

Figure 8

 for one-pipe fuel supply installations. See 

Figure 9

 for two-pipe fuel supply installations.

If fuel supply is 

below

 the fuel unit —

Use a two-pipe oil system when the fuel unit must lift the 
oil more than 8 feet if burner is equipped with a 

B

 fuel unit, 

or more than 2 feet if burner is equipped with an 

H

 fuel 

unit. The return line provided by the two-pipe system is 
needed to purge the air from the fuel lines and minimize the 
likelihood of air-related problems during operation.

y

y

y

Oil Supply Pressure Con-
trol Required

Damage to the pump, fi lter or other compo-
nent seals could cause possible oil leakage 
and potential fi re hazard.

The oil supply inlet pressure to the fuel unit cannot ex-
ceed 3 psig. 
Do NOT install valves in return line.
Ensure that a pressure-limiting device is installed in ac-
cordance with the latest edition of the NFPA 31.

y

y

y

Nozzle pressure

‰

Table 1 - Nozzle Capacities

Rated 

gph 

@  100 

psig

Pressure - pounds per square inch

125 150 175 200 250

275

300

2.00

2.24

2.45

2.65

2.83

3.16

3.32

3.46

2.25

2.52

2.76

2.98

3.18

3.56

3.73

3.90

2.50

2.80

3.06

3.31

3.54

3.95

4.15

4.33

2.75

3.07

3.37

3.64

3.90

4.35

4.56

4.76

3.00

3.35

3.67

3.97

4.24

4.74

4.97

5.20

3.50

3.91

4.29

4.63

4.95

5.53

5.80

6.06

4.00

4.47

4.90

5.29

5.66

6.32

6.63

6.93

4.50

5.04

5.51

5.95

6.36

7.11

7.46

7.79

5.00

5.59

6.12

6.61

7.07

7.91

8.29

8.66

5.50

6.15

6.74

7.28

7.78

8.70

9.12

9.53

6.00

6.71

7.35

7.94

8.49

9.49

9.95

10.39

6.50

7.27

7.96

8.60

9.19

10.28

10.78

11.26

7.00

7.83

8.57

9.26

9.90

11.07

11.61

12.12

7.50

8.39

9.19

9.92

10.61

11.86

12.44

12.99

8.00

8.94

9.80

10.58 11.31

12.65

13.27

13.86

Use only nozzles having the brand, fl ow rate (gph), spray 
angle and pattern specifi ed by the appliance manufac-
turer. 

Follow the appliance manufacturer’s specifi cations for 
the required pump outlet pressure for the nozzle, since 
this affects the fl ow rate. 

Nozzle manufacturers calibrate nozzle fl ow rates at 100 
psig.
This burner utilizes pressures higher than 100 psig, so 
the actual nozzle fl ow rate will be greater than the gph 
stamped on the nozzle body. (Example: A 5.00 gph noz-
zle at 150 psig = 6.12 gph and at 300 psig = 8.66 gph)

For typical nozzle fl ow rates at various pressures see ac-
companying chart.

y

y

Incorrect nozzles and fl ow rates 

could result in impaired combustion, 
under-fi ring, over-fi ring, sooting, 
puff-back of hot gases, smoke and 
potential fi re or asphyxiation haz-
ards. 

Correct Nozzle and Flow 
Rate Required

Summary of Contents for CF1000

Page 1: ...tart up or service work Save this manual for future reference y y y Incorrect installation adjustment or misuse of this burner could result in death severe personal injury or substantial property dama...

Page 2: ...2 Form 6104 BCF10 R06...

Page 3: ...bustion air supply 6 Clearances 6 Fuel supply 6 Nozzle pressure 6 Vent system 7 Electrical supply 7 Verify burner components 7 Verify firing input range 7 Verify air tube 7 Mount the burner 8 10 Mount...

Page 4: ...an If at any time the burner does not appear to be operating properly immediately contact your qualified service agency for consultation We recommend annual inspection service of your oil heating syst...

Page 5: ...asphyxiation explosion or fire Follow These Instructions Exactly 50 Hz motors The burner ratings air settings and nozzle ratings are based on standard 60 hz motors at 3450 rpm Derate all ratings 20 wh...

Page 6: ...r is equipped with an H fuel unit The return line provided by the two pipe system is needed to purge the air from the fuel lines and minimize the likelihood of air related problems during operation y...

Page 7: ...e burner depends on the length of the firing chamber and the distance from the burner center to the chamber floor Verify that the chamber dimensions are at least as large as the minimum values given i...

Page 8: ...unt flange s on air tube Mount air tube to burner Remove the rear access door from the back of the burner for improved access to the interior Attach the air tube to the burner with the bolts and acorn...

Page 9: ...acorn nut d Top acorn nut for setting dim Z only e Indicator adjusting plate f Secondary adjusting plate g Primary adjusting plate Figure 4 Nozzle and nozzle line assembly Measure dimension Z from fro...

Page 10: ...item c Secure the burner to the appliance by tightening the nuts on the burner flange mounting studs Then secure the pedestal support floor flange set screw to the pipe y y y Oil supply return lines I...

Page 11: ...t comply with the latest edition of NFPA 31 Canada CSA B139 and all applicable codes Do not install valves in return line If the oil supply inlet pressure to the pump exceeds 3 psig or for gravity fee...

Page 12: ...ation If any of these items are not clear or are unavailable call Beckett at 1 800 645 2876 for assistance y y y y y Incorrect installation and mishandling of start up could lead to equipment malfunct...

Page 13: ...ing dimension Z only do not loosen after setting dimension Z e Indicator adjusting plate f Secondary adjusting plate g Primary adjusting plate h Copper oil line from oil valve to nozzle line Sequence...

Page 14: ...ialsettingshouldbeadequateforstartingtheburner Tighten the screw to secure the adjusting plate Once the burner is in operation the air setting will be adjusted for best performance as discussed later...

Page 15: ...contact the Fire De partment Carefully follow their directions Keep a fire extinguisher nearby and ready for use y y y y y y Failure to follow these instructions could lead to equipment malfunction an...

Page 16: ...y y y Set air adjusting plate Figure 12 Allow the burner to run until the appliance has warmed sufficiently Visually check the flame The flame should not be dark orange or smoky If the flame appears...

Page 17: ...ectrodes if tips are rounded Inspect the igniter spring contacts Clean the cad cell lens surface if necessary Inspect all gaskets Replace any that are damaged or would fail to seal adequately Inspect...

Page 18: ...Plug Coupling Access Door Use with threaded hole Use with rectangular opening 32439U 16703GY 14 Head assembly CF1000 combustion 51203P 15 Electrode assembly All models 51212 16 Ignition leads 8 1 4 l...

Page 19: ...Form 6104 BCF10 R06 19 Figure 14 Adjustable mount ing plates for CF1000 1 2 3 4 5 6 8 7 13 16 15 14 17 18 19 20 21 22 10 9 11 12 Figure 13 Adjustable Mount ing Plates for CF1000...

Page 20: ...E PROTECTION ASSOCIATION THE LATEST EDITION OF THE NATIONAL FUEL GAS CODE NFPA NO 54 AND IN ACCORDANCE WITH ALL APPLICABLE LOCAL STATE AND NATIONAL CODES HAVING JURISDICTIONAL AUTHORITY Equipment whic...

Reviews: