11
DE
GB
FR
NL
Caution
During all wiring work, the system must be disconnected from the power by removing the CEE plug or
switching off the main switch. Observe the applicable EN guidelines during installation.
3. Motor/control connection
The drive cable (12-wire) must be connected to the appropriate terminals in accordance with the connection plan (not re-
quired if connection has already been carried out by Becker). The terminal designations correspond to the numbers of the
drive cable wires.
The fitted CEE plug can be used as the main switch. If the control is connected without the CEE plug (e.g. permanent con-
nection), a main switch must be connected into the mains feed, which disconnects all the poles according to the overvoltage
category III.
Separate connection cables are required for outdoor use, and for PVC connections these cables have to be laid in a protec-
tive tube.
Control
Checking the running direction
Insert the CEE plug into the CEE socket or switch on the main switch. Now use the UP and DOWN buttons to check whether
the running direction of the door agrees with these commands.
If the running direction does not correspond to the arrow direction:
Remove the CEE plug, or switch the main switch off. Swap the L1 and L3 connections, for example, at the mains connection
terminals (see connection plan). Resume installation.
Setting the end limits
The control is set at the factory so that ascent is carried out in self¬locking mode and descent in deadman’s mode. To facilitate
moving to the final position when setting the limit switches, you can switch the ascent from self¬locking to deadman’s mode
with the DIP switch no.1.
Lower end limit setting
Move the door to the bottom end limit with the DOWN button (deadman’s mode). Approach the desired end limit for the door
by “tapping” if necessary. Set the limit switch cam for DOWN (black) according to the operating instructions for the direct
mount drive used.
Upper end limit setting
Move the door to the top end limit with the UP button (deadman’s mode). Once again, approach the desired top end limit of
the door by “tapping” if necessary. Set the limit switch cam for UP (grey) according to the operating instructions for the direct
mount drive used.
Setting the safety limit switches
The safety limit switches (yellow) are set with approx. 3° delay to the respective operating limit switch. Observe the relevant
information in the operating instructions for the direct mount drive. If a safety limit switch is contacted, the control voltage is
switched off. The relevant control cam must then be turned away manually from the limit switching micro switch, or cleared
by manual activation (e.g. crank).
Setting the function switch S7
With function switch S7 (orange) it is possible to control the relay REL1. A potential-free changeover contact is available via the
output terminals. For example, this enables the the connection of simple traffic light function or a door status display.
Setting of the function switch S8
With function switch S8 (green) it is possible to set a partial opening position of the door which can be activated or deactivated
via an external selector switch.
Note
On principle, the precise adjustment of the limit positions is carried out with the fine adjustment screw of
the respective control cam (please see also the operating instructions for the door drive).
Commissioning of the system
Summary of Contents for S10AF
Page 9: ...9 DE GB FR NL ...
Page 15: ...15 DE GB FR NL ...
Page 21: ...21 DE GB FR NL ...
Page 27: ...27 DE GB FR NL ...
Page 28: ...4023 630 205 0b 02 08 Becker Antriebe GmbH 35764 Sinn Germany www becker antriebe com ...