Deleting both limit positions
Open/close the shading solution to a point between the limit positions.
Press the programming button and keep it pressed.
Then press down the travel button and keep it pressed.
Now release the programming button, but continue to keep the travel button pressed.
Next press the programming button again.
▻
The tubular drive makes a "click click" sound to confirm.
►
Both limit positions are deleted.
Information for the electrician
Tubular drives with electronic limit switching can be connected in parallel. The maximum switching contact load of the switching
equipment (timer, relay control, switch, etc.) must be observed. To operate drives with electronic limit switching, only use switch-
ing elements (timers) that are
not
earthed via the drive. The outputs of the switching element must be potential-free in the neutral
position.
Use external conductor L1 to control the up and down direction. Other devices or consumers (lamps, relays, etc.) must not be dir-
ectly connected to the drive connecting cables. For this purpose, the drives and additional devices must be decoupled by relay
controls.
When installing the drive, all-pole disconnection from the mains with a contact gap of at least 3 mm per pole must be provided (EN
60335).
Attention
Only use mechanically or electrically locked switching elements with a marked zero posi-
tion! This also applies when drives with electronic and mechanical limit switching are used
in the same system. The changeover time for switching the running direction must be at
least 0.5 s. The switch and control must not execute simultaneous UP and DOWN com-
mands. Protect the electrical connections from damp.
Once you have finished wiring everything to the control, ALWAYS check the right direction
assignment of the drive to the control buttons UP and DOWN, EXTEND and RETRACT.
If the drive is to be operated with devices which contain sources of interference, the elec-
trician must ensure suitable interference suppression for the relevant devices.
Torque detection
A correctly installed tubular drive reacts to extraordinarily large increases in load during operation between the limit positions and
thereby prevents an overload of the tubular drive.
Disposal
This product is made of various materials which must be disposed of properly. Find out about the applicable regulations on recyc-
ling or disposal for this product in your country.