6  Maintenance / Service 

The equipment can only be guaranteed to operate safely and reliably in the long term if regular 
inspections and servicing are carried out. These include the following: 
 

For cleaning the devices it is necessary to take care that no electrostatic charging will be done (no 
high volume flow, cleaning only with damp cloth,…) 

 

An inspection includes 

 

  Visual inspection 

o

  Mechanical damage 

o

  Non-permitted dust deposits 

o

  Other irregularities or error messages from the equipment 

  Checking of components (wearing parts) whose functionality or purpose changes and af-

fects the operation of the equipment 

  Documentation of what was done by whom, and when 

 

Maintenance includes 

  Functionality checking 

o

  Operating statuses such as alarms etc. 

  Checking calibration values (= calibration) 

o

  Triggering of alarms by known process parameters (test pressure etc.) 

  Correction of calibration values (= calibration) must be carried out in the factory 
  Documentation of what was done by whom, and when 

6.1  Time intervals 

Inspection: 

The condition of the equipment must be checked at regular intervals. The time interval is extreme-
ly dependent on the local situation and the degree of use, and must therefore be adapted to re-
quirements. Extremely short time intervals can be specified such as once per day, every new shift 
etc.

 

  Defined by the operator in accordance with local requirements 

Maintenance

 

  The interval from the applicable usage regulations must be taken into consideration 
  As a manufacturer we recommend a maximum interval of 1 year 

6.2   Troubleshooting 

A list of possible faults (fault indications) can be found in the table below.  
The table contains an explanation of how to detect faults.  
A list of possible causes and remedial measures also follows.

 

 

Fault indication

 

Possible cause

 

Measures

 

Contact won’t switch

 

Defective diaphragm

 

Replace pressure switch

 

Spring defective

 

Pressure connection blocked

 

Pressure outside working range

 

Summary of Contents for 930...EX Series

Page 1: ...einbeis Stra e 4 71144 Steinenbronn Operating instructions Pressure Switch Model 930 EX Rev 9 Page 1 of 18 Ident 060925 BA 930 R9 2016_englisch_Druckversion doc Operating Instructions The adjustable D...

Page 2: ...rectors Rainer Beck Hans Peter Funk Dr Ernst Thielicke Operating instructions Pressure Switch Model 930 EX Rev 9 Page 2 of 18 1 General instructions 3 1 1 Safety instructions 3 1 1 1 General safety in...

Page 3: ...ngs of the symbols that are used are as follows Useful important additional information Dangers and safety instructions Important please read Failure to comply with these instructions can have a detri...

Page 4: ...d out Dust deposits must be avoided installation location protection cleaning etc in order to prevent dangerous surface temperature increases For the installation procedure it is necessary to take car...

Page 5: ...otentially explosive gasses and dust natural gas bio gas solvents etc Liquid Flammable liquids petrol solvent etc Use in zones in potentially explosive areas Pressure switches are used to monitor the...

Page 6: ...ith the specified zones With intrinsically safe systems i the associated operating materials barrier must al ways be installed outside the potentially explosive area The labelling of the product must...

Page 7: ...1 Pressure connections 2 plastic pipe connection pieces 6 mm P1 for connection to higher pressure P2 for connection to lower pressure 4 2 2 Electrical connections When work is being performed such as...

Page 8: ...km Li 1 mH km Cable routing If there is a risk of mechanical damage the cable must be provided with additional protection protective tube etc The cable diameter must be complied with in order to provi...

Page 9: ...ion must have been performed All interfaces such as inputs and outputs for control purposes must be connected and ready for operation 5 1 Parameterisation Equipment parameterisation Define all applica...

Page 10: ...ues calibration o Triggering of alarms by known process parameters test pressure etc Correction of calibration values calibration must be carried out in the factory Documentation of what was done by w...

Page 11: ...plosive areas No potentially explosive atmosphere is present A release for work must have been issued by the operator The applicable regulations and all documentation for this equipment must be adhere...

Page 12: ...ble ends must be marked and it must be ensured that No electrical voltage is present Unintentional activation is not possible 8 1 Disposal The equipment is made from recyclable materials and is design...

Page 13: ...st 2D 30V 60mA 0 6W Electrical connection Cable conduit M20x1 5 or cap nut conduit with cable strain relief AMP flat plug 6 3 mm x 0 8 mm in accordance with DIN 46244 or push on screw terminals Arrang...

Page 14: ...her Pressure connections 2 plastic pipe connection pieces external diameter 6 0 mm Maximum operating pressure 10 kPa for all pressure ranges Mounting position Switching pressure specifications apply t...

Page 15: ...d drawings and accessories Beck GmbH Druckkontrolltechnik Ferdinand Steinbeis Stra e 4 71144 Steinenbronn Operating instructions Pressure Switch Model 930 EX Rev 9 Page 15 of 18 9 2 Dimensioned drawin...

Page 16: ...Declaration of Conformity Beck GmbH Druckkontrolltechnik Ferdinand Steinbeis Stra e 4 71144 Steinenbronn Operating instructions Pressure Switch Model 930 EX Rev 9 Page 16 of 18 9 3 Declaration of Con...

Page 17: ...trolltechnik Ferdinand Steinbeis Stra e 4 71144 Steinenbronn Operating instructions Pressure Switch Model 930 EX Rev 9 Page 17 of 18 9 4 EC design test certification Note More documentation for EC des...

Page 18: ...for Ignition protection class Zone 2 22 Gc Dc Zone 2 22 1 21 Gb Db Zone 1 2 21 22 Ex ia IIB Ex ia IIIB 0 20 Ga Da Zone 0 1 2 20 21 22 CHARACTERICTICS Intrinsically safe operating materials Associated...

Reviews: