BEA WIZARD II SMR User Manual Download Page 9

10   Troubleshooting (Continued)

1

Troubleshooting Procedures

PROBLEM

PROBABLE CAUSE

CORRECTIVE ACTION

Door will not open (Continued).

2. Wizard not detecting traf

fi

 c.

3. Faulty wiring between sensor and door 

control.

4. Faulty door control.

2. Walk in and out of Wizard detection area, if 

red LED does not illuminate check:

a.  Power supply for Wizard: 12 to 24  VAC 

/ VDC: -5%  to +10%

b.  Check SMR setting on each Wizard. 

The SMR should be disabled unless 

system is being used with BEA’s Door 

Control Unit (DCU).

c. Check Relay Con

fi

 guration for each 

Wizard.

3. Remove all sensor inputs from the door 

control. Jumper the common and activate 

terminals of the door control. If door does 

not open, fault lies within door control or 

motor. Refer to manufacturer’s manual for 

further troubleshooting. If door opens, fault 

lies with sensors or related wiring.

4. Refer to Step 3.

Door keeps recycling open.

1. Wizard is seeing door.

2. Wizard is seeing movement from unwanted 

objects.

3. Vibration is triggering the Wizard.

1. Observe LED status on each Wizard. 

Green LED indicates motion detection, red 

LED indicates presence. If LED’s are on, 

make sensor adjustments as necessary 

to eliminate unwanted detection. Check 

angle, sensitivity, and immunity for 

presence and motion.

2. Check for moving objects in the path of 

detection, such as posters, banners, etc.

3. Locate source of vibration and correct as 

necessary.

Wizard will not respond to remote control.

1. Batteries in remote are dead or are 

installed improperly.

1. Ensure batteries are installed correctly. 

Replace batteries: AAA 1.5 volt.

Wizard will not unlock when access code is 

entered.

1. Improper code being entered.

1. Reset code to the default value of 0000 by 

performing the following:

a.  Cut and restore power supply. No code 

is required to unlock during the 

fi

 rst 

minute after powering. Reset code prior 

to locking.

Red LED is 

fl

 ashing rapidly after attempting 

setup.

1. Detection 

fi

 eld was violated during setup of 

the Wizard.

1. Launch a new setup and insure that the 

detection 

fi

 eld remains all clear until setup 

is complete.

2. Wizard may be seeing the door as it is 

closing. Adjust infrared curtain and launch 

a new setup.

Wizard will not detect – door stays open.

1. Improper SMR setting.

1. If the Wizard is NOT being used with a 

BEA DCU, set SMR to a value of 0. 

12   Company Contact

Do not leave problems unresolved. If a satisfactory solution cannot be achieved after troubleshooting a problem, please 
call BEA, Inc.  If you must wait for the following workday to call B.E.A., leave the door inoperable until satisfactory 
repairs can be made.   Never sacri

fi

 ce the safe operation of the automatic door or gate for an incomplete solution.

The following numbers can be called 24 hours a day, 7 days a week.  For more information, visit www.beasensors.com.

West:

South-East:

US and Canada:

1-888-419-2564
1-800-407-4545
1-866-249-7937

Mid-West:

North-East:

Canada:

1-888-308-8843
1-866-836-1863
1-866-836-1863

11   Accessories

Ceiling Adapter

10WCA

Universal Rain Cover

10URC

Spot

fi

 nder

10SPOT

Cable Adapter

20.5048

75.5122.05 

20070427 

          

Page 

of 

13

OBSOLETE

Summary of Contents for WIZARD II SMR

Page 1: ...55 lbs 250 g Housing material ABS LURAN S Color of Housing Anthracite gray standard aluminum or white finish Cable length 10 of 9 conductor cable 2nd Radar Antenna Radar Motion Sensor Radar Antenna Clip Radar Tilt Angle Indication 15 30 45 Cover Push Buttons IR Presence Sensor IR Prism Main Connector IR Curtain Adjustment Screw DESCRIPTION MOTION SENSOR PRESENCE SENSOR Technology Microwave and mic...

Page 2: ...uipment ensure the correct line voltage and stability When applying equipment on a new installation utilizing new electrical supply circuits always ensure that correct line voltage exists and is stable Remember to shut the power back off after this is checked and before performing any wiring to the system 5 Installation 1 Remove Sensor Cover 1 Remove cover from unit by gently prying the tab on the...

Page 3: ...ilot holes for screw mounting NOTE Flush mount with bottom of header is necessary for all negative IR angles 2 Mount the sensor at a maximum height of 2 from the bottom line of the door operator 3 Insert mounting screws approximately halfway in and install the Wizard on the screws When in place tighten screws to secure to header NOTE Leave cover off until mechanical adjustments are complete 3 Cabl...

Page 4: ...pattern further away from the door Be certain to walk test the detection field and ensure compliance with applicable ANSI standards 0 3 2 6 4 3 2 6 4 0 3 2 6 4 9 6 0 3 2 6 4 3 2 6 4 0 3 2 6 4 9 6 13 1 15 30 45 30 45 15 0 3 IR Presence Sensing Field Width 1 Install the lens for the desired IR pattern The wide pattern offers 2 curtains of 24 overlapping spots and the narrow pattern offers 2 curtains...

Page 5: ...shes Quickly Press Question Mark The Number of Green Flashes Indicate the Value of This Parameter RED LED Flashes Slowly Press Lock Key Twice OR Lock Code 0 9 0 9 0 9 0 9 1 4 7 F1 F2 5 8 0 3 6 9 2 Relay Hold Time 0 0 5s 9 9s Sensitivity 0 min 9 max default 7 0 3 6 9 0 3 2 6 4 3 2 6 4 0 3 2 6 4 9 6 Microwave Detection Mode 1 Bidirectional Mode 2 Unidirectional Mode 3 Unidirectional Mode with MTF 4 ...

Page 6: ...mmended for first time set up Duration is 16 seconds and will automatically trigger door to open position during set up routine Microwave Immunity Immunity levels above 3 are intended for applications where excessive interference may be causing unintended detection When applying a value of 4 or higher increment the value one step at a time followed by a walk test When complete ensure compliance wi...

Page 7: ... RED LED PARAMETER VALUES Altered by the left button and confirmed by GREEN LED DEFAULT VALUE 1 Radar Sensitivity 0 9 7 2 Relay hold time 0 9 0 3 Output configuration 1 4 4 4 Auto learn presence sensing 0 9 0 5 Detection mode 1 4 3 6 Microwave Immunity 1 9 3 7 IR Immunity 1 3 2 8 Not Used Displays 8 Orange Flashes Displays 8 Orange Flashes 9 SMR mode 0 1 0 10 IR curtain 1 3 3 11 Secondary Sensitiv...

Page 8: ...Wizard 3 Faulty Power Input 1 Launch a new setup and remain all clear from the detection area 2 Remove power then re apply Input power may have fluctuated beyond tolerances Red LED on at Wizard 1 Wizard in detection 1 If red LED is on at Wizard a Adjust infrared pattern away from the door and launch a new set up Refer to page 5 for infrared adjustments Use BEA Spotfinder to accurately adjust the p...

Page 9: ...emote are dead or are installed improperly 1 Ensure batteries are installed correctly Replace batteries AAA 1 5 volt Wizard will not unlock when access code is entered 1 Improper code being entered 1 Reset code to the default value of 0000 by performing the following a Cut and restore power supply No code is required to unlock during the first minute after powering Reset code prior to locking Red ...

Page 10: ...4 5 NC 4 NO 3 COM 2 12 24 VAC DC 1 12 24 VAC DC RB WH 1 RB BL 2 EB WH 3 EB BL 4 RECEIVER A EMITTER A RECEIVER B EMITTER B WH WHITE BL BLACK MICROCELL ONE ON 1 2 3 4 RA WH 1 RA BL 2 EA WH 3 EA BL 4 5 NC 4 NO 3 COM 2 12 24 VAC DC 1 12 24 VAC DC RB WH 1 RB BL 2 EB WH 3 EB BL 4 RECEIVER A EMITTER A RECEIVER B EMITTER B WH WHITE BL BLACK MICROCELL ONE ON 1 2 3 4 IF AFTER TROUBLESHOOTING A PROBLEM A SAT...

Page 11: ...tional connect to reset TB1 R if required LOCKING DEVICE TITLE BESAM CUD J 9 AMD2 SLIDING DOOR WITH WIZARD II SYSTEM NOTE 1 DO NOT CONNECT BROWN WIRES TO C SWITCH COMMON 2 OBSERVE POLARITY WITH BROWN CONNECTING TO GROUND 0 VDC 3 A JUMPER MUST BE INSTALLED IN PINS 9 12 ON CONTROL BOX FOR RE ENTRY SENSOR IN ONE WAY TRAFFIC AS PER APPLICABLE ANSI STANDARD IF AFTER TROUBLESHOOTING A PROBLEM A SATISFAC...

Page 12: ... CONNECTED TO GROUND 0 VDC 3 A JUMPER MUST BE INSTALLED BETWEEN PINS 5 12 ON THE CONTROL BOX TO ALLOW FOR RE ENTRY SENSOR IN ONE WAY TRAFFIC MODE TO COMPLY WITH ANSI A156 10 SECTION 8 3 3 4 CAN POWER SENSOR FROM CONTROL BOX 24 V TRANSFORMER IF AFTER TROUBLESHOOTING A PROBLEM A SATISFACTORY SOLUTION CANNOT BE ACHIEVED PLEASE CALL B E A INC FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1 80...

Page 13: ...6 7 8 9 10 11 12 13 14 15 16 INTERIOR SW EXTERIOR SW COMMON SAFETY BEAM COMMON TOGGLE SW COMMON CLS MON SW COMMON PARTIAL OPEN 2WAY 1 WAY NIGHT SW COMMON DAY NITE SW 24VDC 24VDC C2150 CONTROL WIZARD EXTERIOR WIZARD INTERIOR IF AFTER TROUBLESHOOTING A PROBLEM A SATISFACTORY SOLUTION CANNOT BE ACHIEVED PLEASE CALL B E A INC FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1 800 523 2462 FROM 8...

Reviews: