5   Installation - Mechanical & Electrical

LOCK ST

ATUS SWITCH (SPDT)

POWER 

SUPPL

Y  

     +    -

POWER

SELECT

OR

JUMPER

LED

MAG BOND SENSOR

MAGNET

TIMER (0-90 SEC)

TYPICAL INSTALLATION

NOTE:  DO NOT over-tighten the armature plate.  The rubber washer is designed to allow the armature 

plate to automatically adjust position for best mating position between the lock and armature plate.

DOOR FRAME

ARMATURE PLATE

MAGNET

ANGLE

BRACKET

MOUNTING

PLATE

MOUNTING

PLATE

STRINGER

HOLE FOR

GUIDE PIN
HOLE FOR NUT

RUBBER WASHER
STEEL WASHER
ARMATURE PLATE
SCREW M8 (35MM)

GUIDE PIN

DOOR

NUT

SPACER

WASHER

ARMATURE

PLATE

DOOR

NUT

DOOR FRAME

DOOR FRAME

DOOR

ARMATURE PLATE

ARMATURE PLATE

MAGNET

MAGNET

DOOR

DOOR

MOUNTING

PLATE

CAUTION:  Observe proper 

circuit board orientation!

NOTE:  The product must be powered from a UL listed, regulated, power limited, power supply.
NOTE:  If power switch is not wired between DC source voltage and magnet,

             it will take a longer time to de-energize the magnet simulating residual magnetism.

1. 12 VDC INPUT
  

A.   Required power 0.5A (Max).
B.   Connect ground (-) lead from a 12 VDC power source to Terminal 2.
C.   Connect positive (+) lead from a 12 VDC power source to Terminal 1.
D.   Check jumper for 12 VDC operation.

2. 24 VDC INPUT

A.   Required power 0.25A (Max).
B.   Connect ground (-) lead from a 24 VDC power source to Terminal 2.
C.   Connect positive (+) lead from a 24 VDC power source to Terminal 1.
D.   Check jumper for 24 VDC operation.

3. CONTACTS

1.   Relay dry contacts are rated 1A at 24 VDC for safe operation, DO NOT exceed this 

rating.

2.   If a NO switch is required, connect the wires from the system to Terminal 4 & Terminal 3.
3.   If a NC switch is required, connect the wires from the system to Terminal 4 & Terminal 5.

DS VERSION

24/7 Tech Support: 1-800-407-4545 | Customer Service: 1-800-523-2462 | General Tech Questions: [email protected] | Tech Docs: www.beasensors.com

75.5366.08 UL MAGLOCKS 600lb 20210806   

Page 3 of 4

CIRCUIT BOARD

NOTE:  Terminals ratings:  12~24AWG

7   Installation 

 Electrical

CAUTION!  Observe 

proper circuit board 

orientation!

+  -

G

   1      2         3      4      5
   +      -        NO    C     NC

12VDC

24VDC

POWER 

SELECTOR

JUMPER

0 - 90 SEC.

RELOCK TIMER

POWER 
SUPPLY
    +      - 

LOCK STATUS RELAY (SPDT)

Align the black, plastic piece of the 

armature plate with the cover plate (i.e. 

magnet must line up with the switch).

6   Armature Plate Installation

Hole For Guide Pin

Hole For Nut

Steel Washer

Rubber Washer

Steel Washer

Armature Plate

Nut

Spacer

           Door

Screw  M8  35mm

Guide Pin

The product must be powered from a UL-listed, regulated, power-limited, power supply.
If power switch is not wired between DC source v) and magnet, it will take a longer time 

to de-energize the magnet simulating residual magnetism.
Dual MAGLOCK models have two circuit boards that must both be powered; repeat these steps 

on each side.

12 VDC INPUT

 - Required power:  See Specifications on page 2.

 - Connect positive (+) lead from a 12 VDC power source to Terminal 1.
 - Connect negative (-) lead from a 12 VDC power source to Terminal 2.

 - Check jumper for 12 VDC operation.

24 VDC INPUT

 - Required power:  See Specifications on page 2.

 - Connect positive (+) lead from a 24 VDC power source to Terminal 1.
 - Connect negative (-) lead from a 24 VDC power source to Terminal 2.

 - Check jumper for 24 VDC operation.

+  -

G

   1      2         3      4      5
   +      -        NO    C     NC

12VDC

24VDC

POWER 

SELECTOR

JUMPER

0 - 90 SEC.

RELOCK TIMER

POWER 
SUPPLY
    +      - 

LOCK STATUS RELAY (SPDT)

POWER

Summary of Contents for UL MAGLOCKS 600LB

Page 1: ... 1 Description DESCRIPTION 10MAGLOCK3UL 10MAGLOCK3ULDS 10MAGLOCK6UL 10MAGLOCK6ULDS Lock single dual Input Voltage 12 or 24 VDC 12 or 24 VDC Relay Rating 1 0 A 24 VDC resistive 1 0 A 24 VDC resistive Reed Switch Rating SPDT 0 5 amp 30 VAC VDC resistive SPDT 0 5 amp 30 VAC VDC resistive Power Consumption 505 mA 12 VDC 260 mA 24 VDC 505 2 mA 12 VDC 260 2 mA 24 VDC Dimensions 9 84 x 1 65 x 1 02 in 250...

Page 2: ...ocking efficiency 5 The maglock mounts rigidly to the door frame The armature plate mounts to the door with the hardware provided This allows the armature plate to pivot about its center to compensate for door wear and misalignment 5 Template use must take place with the door in its normally closed position 5 Add threadlocker to all screws before installing and firmly tighten screws 5 Install only...

Page 3: ...black plastic piece of the armature plate with the cover plate i e magnet must line up with the switch 6 Armature Plate Installation Hole For Guide Pin Hole For Nut Steel Washer Rubber Washer Steel Washer Armature Plate Nut Spacer Door Screw M8 35mm Guide Pin The product must be powered from a UL listed regulated power limited power supply If power switch is not wired between DC source voltage and...

Page 4: ...LIGHT COM REED SWITCH ON DOOR STATUS SENSOR SWITCH Switch changes state when door is open NO BEA Inc the sensor manufacturer cannot be held responsible for incorrect installations or incorrect adjustments of the sensor device therefore BEA Inc does not guarantee any use of the sensor device outside its intended purpose BEA Inc strongly recommends that installation and service technicians be AAADM ...

Reviews: