 75.1041.08 LO21U 20150708 

 

Page 5 of 5 

COMPANY 
CONTACT

 

TROUBLE-
SHOOTING 

 

SET-UP 
INSTRUCTIONS – 
Cont. 

 
 

8. 

When all functions of the control and LO-21U have been confirmed, the lockout time delay will need to be set. Time 
delay is set by using dipswitches 1 through 5. Perform the following steps: 

q

  Activate the door to the open position. 

q

  Allow the door to close and count how many seconds it takes for the overall door closing cycle  

q

  Configure the dip switches according to the chart on Page 3 for the lock out time that is required 

q

  Activate the door again to the open position 

q

  Stand outside of the Bodyguard detection pattern, and while the door is closing, observe the red LED on 

the Bodyguard 

q

  The red LED on the Bodyguard should NOT illuminate during the closing cycle. If it does, it is probably 

seeing the door at the very last degree or two of door closing, which would indicate that the lock out time 
needs to be slightly increased. 

q

  Reconfigure the dipswitches to add 1 second of lock out time.  

q

  When the lock out time is correct. The red LED will not illuminate during the entire closing cycle of the 

door.  

q

  The last test is to insure that the Bodyguard detects an object as soon as the door has stopped closing. 

Simply  allow  the  doors  to  begin  closing,  and  step  in  behind  the  doors,  into  the  Bodyguards  field  of 
detection (be sure to NOT break the path of the lockout safety beams, if so equipped). The red LED shall 
illuminate  and  remain  on  at  the  Bodyguard,  and  at  the  LO-21U,  as  soon  as  the  door  reaches  the  fully 
closed position, provided that an object remains in the Bodyguard’s detection field. 

 
 
 
 

With the door closed, the RED 
LED  does  not  come  on  upon 
Bodyguard detection. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

  Note: Lockout Relay will not function correctly when power close function is enabled on the door control.

 

 

 

If after troubleshooting a problem, a satisfactory solution cannot be achieved, please call B.E.A., Inc. 
for further assistance during

 Eastern Standard Time at 1-800-523-2462 from 7am - 5pm.  

For after-hours, call East Coast: 1-866-836-1863 or 1-800-407-4545 / Mid-West: 1-888-308-8843 /  
West Coast: 1-888-419-2564 
DO NOT 

leave any problem unresolved. If you must wait for the following workday to call B.E.A., leave the door inoperable 

until satisfactory repairs can be made. 

NEVER

 sacrifice the safe operation of the automatic door or gate for an incomplete solution. 

Web: www.beasensors.com

 

 

 

  

PROBLEM                                                  PROBABLE CAUSE                               CORRECTIVE ACTION 

 
 
 
 
 
 
 
 
 
 
With the door closed, the 
GREEN LED comes on upon 
Bodyguard detection. 
 
 
 
 
 
With the door open, the 
GREEN LED does not come 
on upon Bodyguard 
detection. 
 

No Power applied to the Brown (+) 
and Orange (-) wires. 

Or 

The Gray and Violet wires are not 
properly connected to the 
Bodyguard pins 3,4. 
 
 
 
 
 
 

 

 

 
 
Dipswitch# 6 is in the wrong 
position. 
 
 
 
 
 
 
Reversed polarity or no motor 
voltage on the RED and BLACK 
wires. 

 Step 1

. Check for power 12-24 VAC / 15-24 VDC 

on  the  Brown  (+)  and  Orange  (-)  wires  with  a 
meter.  If voltage is there go to Step 2. 

 Step 2

. Jumper across Bodyguard connector pins 

3,4. 

  RED LED does not come on, go to Step 3. 

  RED LED comes on, go to Step 4. 

**Step  3

.  Check  continuity  with  a  meter  on  the 

Orange,  Brown,  Violet  and  Gray  wires  from  the 
back  of  the  harness  connector  to  the  ends  of  the 
wire.  Correct  any  problem  connections.  If  no 
problem connections are found, replace LO21U. 
 

Step 4.

 Check Bodyguard Relay Mode function is 

set to 1.  If OK replace Bodyguard. 
 

Step 1

. Check that Dipswitch# 6 is set correctly for 

the application. 

Step  2

.  Remove  harness  from  lockout  and  re-

install (this resets the LO21U).   

Step  3

.  Check  motor  voltage  in  door  closed  and 

open position. Call Technical support. 
 

Step  1

.  Check  Dipswitch#  6  is  correct  for 

application.   

**Step  2

.    Check  RED  and  BLACK  wire 

connections  at  the  motor  or  source  of  door  open 
voltage.  Correct any problem connections. 

Step 3

. Reverse RED and BLACK LO21U wires at 

the motor. 
 

No LED display on the LO21U or 
Bodyguard and door will not 
open. 

Dipswitch# 7,8 are in the wrong 
position. 
 
 

Step  1

.  Check  Dipswitches#  7,8  for  proper 

position for application.  

Step  2

.  Check  control  box  connections  for  the 

Yellow, Green and Blue wires.  
 
** Remove power from sensors and door control 
before performing these checks.. 

OBSOLETE

Summary of Contents for LO-21U

Page 1: ... 24 VDC Operating frequency 4 MHz Microprocessor Power consumption 10 mA at rest 50 mA Maximum Output 2 SPST Relays Maximum voltage Relay contacts 60 VDC 120 VAC Maximum current Relay contacts 2A DC 0 5 A AC Shut off all power going to the header before attempting any wiring procedures Maintain a clean safe environment when working in public areas Constantly be aware of pedestrian traffic around t...

Page 2: ... DC Green Door Control Common Blue Door Control Activate Yellow Door Control Safety 1 The dipswitches are located at the end of the LO 21U opposite of the wire connection terminal There are 8 positions available Dipswitch designations are as follows BLANK 1 INHIBIT GND 2 INHIBIT 3 N C 4 N O 5 COM 6 POWER 7 POWER 8 BLANK 1 INHIBIT GND 2 INHIBIT 3 N C 4 N O 5 COM 6 POWER 7 POWER 8 115 VAC BODYGUARD ...

Page 3: ... 0 seconds 1 second 2 Time Delay 2 sec value 0 seconds 2 second 3 Time Delay 4 sec value 0 seconds 4 second 4 Time Delay 8 sec value 0 seconds 8 second 5 Time Delay 16 sec value 0 seconds 16 second 6 Voltage switching device Voltage source is other than motor Motor Voltage 7 Safety circuit logic used with DS 8 7 OFF 8 ON N O Safety Circuit 8 Safety circuit logic used with DS 7 7 ON 8 OFF N C Safet...

Page 4: ...wires Also make sure the LO 21U has the proper input voltage at the orange and brown wires 5 Once the Bodyguard is functioning correctly with regard to the open and closed door setup walk testing may begin q Do NOT proceed with walk test until the Bodyguard is functioning correctly 6 The LO 21U has two LED s to indicate what function it is performing When the door is closed and someone steps into ...

Page 5: ...62 from 7am 5pm For after hours call East Coast 1 866 836 1863 or 1 800 407 4545 Mid West 1 888 308 8843 West Coast 1 888 419 2564 DO NOT leave any problem unresolved If you must wait for the following workday to call B E A leave the door inoperable until satisfactory repairs can be made NEVER sacrifice the safe operation of the automatic door or gate for an incomplete solution Web www beasensors ...

Reviews: