5.7.
Return the handle to its original position and then pull briskly.
5.8.
After starting, allow the recoil starter handle to return to its original position with the
handle still in your hand.
If the engine fails to start after several attempts, repeat the
starting procedures mentioned above with the engine choke
switch placed in the OFF position.
5.9.
After 20 to 30 seconds of warm-up, turn the engine choke switch to "OFF" position.
6. RCD TESTING - AC USE
6.1.
To test the RCD receptacle on the unit, apply a test load or lamp to each AC outlet to verify
output. Then push the test button.
6.1.1.
The reset button should pop out and there should be no power at the receptacle.
6.1.2.
If the reset button does not pop out then you MUST NOT continue to use the
generator.
6.1.3.
If the RCD DOES NOT reset properly, do not use the receptacle. See service provider
for service immediately.
6.1.4.
If RCD tests correctly, firmly push the reset button to restore power. A distinctive
click should be heard or felt when this is complete.
6.2.
You can now continue to apply loads to the unit.
Page 12