Operating Manual
Digital Field Display PA 440
Headquarters
BD SENSORS GmbH
BD-Sensors-Str. 1
D - 95199 Thierstein
Germany
Tel.: +49 (0) 9235-9811-0
Fax: +49 (0) 9235-9811-11
Eastern Europe
BD SENSORS s.r.o.
Hradištská 817
CZ - 687 08 Buchlovice
Czech Republic
Tel.: +42 (0) 572-4110 11
Fax: +42 (0) 572-4114 97
Russia
BD SENSORS RUS
39a, Varshavskoe shosse
RU - Moscow 117105
Russia
Tel.: +7 (0) 95-380 1683
Fax: +7 (0) 95-380 1681
China
BD SENSORS China Co, Ltd.
Room B, 2nd Floor, Building 10,
No. 1188 Lianhang Rd.
201112 Shanghai,
China
Tel.: +86 (0) 21-51600 190
Fax: +86 (0) 21-33600 613
further agencies in:
EUROPE
•
Belgium
•
Denmark
•
Finland
•
France
•
Great Britain
•
Greece
•
Italy
•
Lithuania
•
Luxemburg
•
Netherlands
•
Norway
•
Poland
•
Portugal
•
Romania
•
Sweden
•
Switzerland
•
Slovakia
•
Spain
•
Turkey
•
UK
•
Ukraine
AFRICA
•
Egypt
•
South Africa
ASIA
•
India
•
Iran
•
Israel
•
Japan
•
Kazakhstan
•
Malaysia
•
Singapore
•
Taiwan
•
Thailand
•
Vietnam
AUSTRALIA
The addresses of our distribution partners are listed on our
homepage
www.bdsensors.com
. It is possible to download
data sheets, operating manuals, ordering codes and certifi-
cates, as well.
1. General information
1.1 Information on the operating manual
This operating manual contains important information on
proper usage of the device. Read this operating manual
carefully before installing and starting up the pressure
measuring device.
Adhere to the safety notes and operating instructions which
are given in the operating manual. Additionally applicable
regulations regarding occupational safety, accident preven-
tion as well as national installation standards and engineer-
ing rules must be complied with!
This operating manual is part of the device, must be kept
nearest its location, always accessible to all employees.
This operating manual is copyrighted. The contents of this
operating manual reflect the version available at the time of
printing. It has been issued to our best knowledge. BD
SENSORS is not liable for any incorrect statements and their
effects.
– Technical modifications reserved –
1.2 Symbols used
DANGER! – dangerous situation, which may result in
death or serious injuries
WARNING! – potentially dangerous situation, which
may result in death or serious injuries
CAUTION! – potentially dangerous situation, which may
result in minor injuries
!
CAUTION! – potentially dangerous situation, which may
result in physical damage
NOTE – tips and information to ensure a failure-free
operation
1.3 Target group
WARNING! To avoid operator hazards and damages of
the device, the following instructions have to be worked
out by qualified technical personnel.
1.4 Limitation of liability
By non-observance of the operating manual, inappropriate
use, modification or damage, no liability is assumed and
warranty claims will be excluded.
1.5 Intended use
- The field display PA 440 is supplied by the analogue
current loop and shows the measured value on the dis-
play. For monitoring the limit values optionally up to two
PNP open collector-contacts are available. As standard
the PA 440 is equipped with a LC-display, optionally a
LED-display is deliverable.
- The configuration is menu-driven via two push buttons
located in the front. Following parameters could be con-
figured: decimal point, zero point, end point, switch-on
and switch-off points, etc. Those parameters are being
stored in an EEPROM and, thus, are being kept also in
case of power breakdown. Limit exceeding in both direc-
tions can be displayed as a message. Furthermore an
access protection is provided.
- It is the operator's responsibility to check and verify the
suitability of the device for the intended application. If
any doubts remain, please contact our sales department
in order to ensure proper usage. BD SENSORS is not
liable for any incorrect selections and their effects!
- The technical data listed in the current data sheet are
engaging and must be complied with. If the data sheet is
not available, please order or download it from our
homepage. (http://www.bdsensors.com/products/down-
load/datasheets)
WARNING!
Danger through improper usage!
1.6 Package contents
Please verify that all listed parts are undamaged included in
the delivery and check for consistency specified in your
order:
- field display PA 440
- sheet of unit labels
- mounting instructions
1.7 UL – Approval
The UL – Approval was done with respect to U.S. standards
norms which also correspond with the applicable Canadian
standards norms for safety.
Note the following points, so that devices fulfils the demands
of UL approval:
- The transmitter shall be supplied by Limited Energy
Source (per UL 61010) or NEC Class 2 Power Source.
- only indoor use
- maximum operating voltage: see technical data
- use only batteries with UL certification
2. Product identification
The device can be identified by its manufacturing label. It
provides the most important data. By the ordering code the
product can be clearly identified. The programme version of
the firmware, (e. g. P06) will appear for about 1 second in
the display after starting up the device. Please hold it ready
for inquiry calls.
Fig. 1 manufacturing label
!
The manufacturing label must not be removed from the
device!
3. Mechanical installation
3.1 Mounting and safety instructions
WARNING!
Install the device only when currentless!
WARNING!
This device may only be installed by
qualified technical personnel who has read and under-
stood the operating manual!
!
Handle
this
high-sensitive
electronic
precision
measuring device with care, both in packed and
unpacked condition!
!
There are no modifications/changes to be made on the
device.
!
Do not throw the package/device!
!
Remove packaging only directly before starting up the
device to avoid any damage!
!
Do not use any force when installing the device to
prevent damage of the device and the transmitter!
3.2 General installation steps
- Carefully remove the pressure measuring device from
the package and dispose of the package properly.
- Next the field display has to be mount stationary on a
suitable fixing location via two appropriate fastening
screws.
3.3 Lead in the transmitter cable
- Lead in the connecting cable of the transmitter through
the cable gland on the left side. The cable length inside
the terminal box has to be long enough for connecting
the cords with the terminal clamps on the left
(SENSOR).
- Then tighten the cable gland by hand. Take care that
the cable is strain-relieved.
- Pay attention that the PTFE-filter on the gauge refer-
ence of BD SENSORS-transmitters may not be dam-
aged or removed.
3.4 Lead in the supply line
- Lead the supply line through the cable gland on the
right side. The cable length inside the terminal box has
to be long enough for connecting the cords with the
terminal clamps on the right (SUPPLY).
- Then tighten the cable gland by hand. Take care that
the cable is strain-relieved.
4. Electrical Installation
WARNING!
Install the device only when currentless!
The supply must correspond to the safety class II
(protective insulation)!
The transmitter shall be supplied by Limited Energy
Source (per UL 61010) or NEC Class 2 Power Source!
Open the top cover; establish the electrical connection of
the device according to the following table and the wiring
diagram. Screw the top cover onto the box again.
Pin configuration:
De-
sign-
ation
Terminal
block
Electrical
connection
(cable colours of
BD SENSORS
transmitters)
to connected with
GND SENSOR
Potential reference
clamp
(yellow/green )
cable shield of
transmitter
VS- SENSOR
Supply - (brown)
neg. connecting
cable of transmitter
VS+ SENSOR
(white)
pos. connecting
cable of transmitter
SP2
SP
Contact 1
connecting cable
of transmitter
for contact 1
SP1
SP
Contact 2
connecting cable
of transmitter
for contact 2
VS+ SUPPLY
pos. connecting
cable for pressure
signal
VS- SUPPLY
Supply -
neg. connecting
cable for pressure
signal
GND SUPPLY
Potential
reference clamp
cable shield of
supply line
For the electrical connection a shielded and twisted
multicore cable is recommended.
The ground wires of all components have to be
connected when installing!
Supply:
The supply created by the electronics of the device is
approx. 6.5 V
DC
. Please take this into consideration when
planning your power supply. The tolerances for the power
supply can be calculated as follows:
Minimum supply:
V
S
min
=
V
min
TR
+ 6.5V
Maximum supply:
V
S
max
=
V
max
TR
+ 6.5V
V
min TR
= minimum supply of the used 2-wire transmitter
V
maxTR
= maximum supply of the used 2-wire transmitter
www.bdsensors.com
EN
input
type
serial
designation
number
output
ordering code